Bit
Bit = 0
Bit =1
00
OFF 1
ON 1
01
OFF 2
ON 2
02
OFF 3
ON 3
03
Motor coasting
Enable
04
Quick-stop
Ramp
05
Freeze output frequency
Ramp enable
06
Ramp stop
Start
07
No function
Reset
08
Jog 1 OFF
ON
09
Jog 2 OFF
ON
10
Data not valid
Valid
11
No function
Slow down/Relay 123/
Digital output terminal
9
12
No function
Catch-up/Relay 123
13
Setup 1
Setup 2
14
15
No function
Reversing
Table 3.23
NOTICE
The use of Bit 00, Bit 01 and Bit 02 for switching off the
power supply (by use of relay) will require a separate
power on. This because there is no 24 #V external
connection to supply the FCM 300 control, which is
required to activate the FCM 300 again via input signal.
Bit 00, OFF1/ON1
An ordinary ramp stop which uses the ramp time in
parameters 207/208. Bit 00 = "0" leads to a stop. Bit 00 =
“1” means that the frequency converter will be able to
start if the other conditions for starting have been fulfilled.
Bit 01, OFF2/ON2
Coasting stop. Bit 01 = "0" leads to a coasting stop. Bit 01
= "1" means that the frequency converter is able to start,
provided the other conditions for starting have been
fulfilled.
Bit 02, OFF3/ON3
Quick-stop, which uses the ramp time in parameter 212.
Bit 02 = "0" leads to a quick-stop. Bit 02 = "1" means that
the frequency converter is able to start, provided the other
conditions for starting have been fulfilled.
Bit 03, Coasting/enable
Coasting. Bit 03 = "0" leads to a stop. Bit 03 = "1" means
that the frequency converter is able to start, provided the
other conditions for starting are fulfilled.
NOTICE
In parameter 502 the choice is made as to how bit 03 is
to be combined (gated) with the corresponding function
in the digital inputs.
Bit 04, Quick-stop/ramp
Quick-stop which uses the ramp time in parameter 212. Bit
04 = "0" leads to a quick-stop. Bit 04 = "1" means that the
frequency converter is able to start, provided the other
conditions for starting are fulfilled.
NOTICE
In parameter 503 the choice is made as to how bit 04 is
to be combined (gated) with the corresponding function
on the digital inputs.
Bit 05, Freeze output frequency/ramp enable
Bit 05 = "0" means that the given output frequency is
maintained even if the reference is changed. Bit 05 = "1"
means that the frequency converter is again able to
regulate, and the given reference is followed.
Bit 06, Ramp stop/start
An ordinary ramp stop that uses the ramp time in
parameters 207/208. Bit 06 = "0" leads to a stop. Bit 06 =
"1" means that the frequency converter is able to start,
provided the other conditions for starting have been
fulfilled.
NOTICE
In parameter 505 the choice is made as to how bit 06 is
to be combined (gated) with the corresponding function
on the digital inputs.
Bit 07, No function/reset
Reset of trip. Bit 07 = "0" means that there is no reset. Bit
07 = "1" means that a trip is reset. After reset it will take
approx. 1.5 second until the unit is ready. The status word
will indicate the ready state.
Bit 08, Jog 1 OFF/ON
Activation of pre-programmed speed in parameter 509
(Bus JOG 1). JOG 1 is only possible when Bit 04 = "0" and
bit 00-03 = "1".
Bit 09, Jog 2 OFF/ON
Activation of pre-programmed speed in parameter 510
(Bus JOG 2). JOG 2 is only possible when Bit 04 = "0" and
Bits 00-03 = "1". If both JOG 1 and JOG 2 are activated
(Bits 08 and 09 = "1"), JOG 1 has the higher priority, which
Programming
VLT
®
DriveMotor FCM Series
64
MG03BA02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT Brook Crompton Motor FCM 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Brook Crompton Motor FCM 300 www danfoss com drives...
Страница 2: ......
Страница 26: ...Illustration 2 5 Installation VLT DriveMotor FCM Series 24 MG03BA02 VLT is a registered Danfoss trademark 2 2...
Страница 37: ...Programming VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 35 3 3...
Страница 101: ...Index VLT DriveMotor FCM Series MG03BA02 VLT is a registered Danfoss trademark 99...
Страница 102: ...www danfoss com drives MG03BA02 175R0087 MG03BA02 Rev 2011 12 22...