Type designation
P11K
P15K
P18K
P22K
P30K
Continuous (3x551–690 V) [A]
10
13
13
18
18
22
22
27
27
34
Intermittent (60 s) (3x551–690 V) [A]
16
14.3 20.8 19.8 28.8 24.2 35.2 29.7 43.2 37.4
Continuous kVA at 550 V [kVA]
10
13.3 13.3 18.1 18.1 21.9 21.9 26.7 26.7 34.3
Continuous kVA at 690 V [kVA]
12
15.5 15.5 21.5 21.5 26.3 26.3 32.3 32.3 40.6
Maximum input current
Continuous 550 V [A]
9.9
15
15
19.5 19.5 24
24
29
29
36
Intermittent (60 s overload) (3x525–550 V) [A]
15.8 16.5 23.2 21.5 31.2 26.4 38.4 31.9 46.4 39.6
Continuous (3x551–690 V) [A]
9.0
14.5 14.5 19.5 19.5 24
24
29
29
36
Intermittent (3x551–690 V) [A]
14.4 16
23.2 21.5 31.2 26.4 38.4 31.9 46.4 39.6
Additional specifications
Maximum cable cross–section
(2)
for mains, motor, brake, and
load sharing [mm
2
(AWG)]
35, 25, 25 (2, 4, 4)
Maximum cable cross–section
()
for mains disconnect [mm
2
(AWG)]
6, 10, 10 (6, 8, 8)
Estimated power loss
(3)
at rated maximum load [W]
(4)
150
220
150
220
220
300
300
370
370
440
Efficiency
(5)
0.98
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
3
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
.
4
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
. For efficiency class see
.
5
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
. For efficiency class see
.
Table 41: Enclosure, Mains Supply 3x525–690 V AC IP20/IP21/IP55 – Chassis/NEMA1/NEMA 12, P37K–P75K
Type designation
P37K
P45K
P55K
P75K
(1)
P90K/N90K
(1)
High/normal overload
(2)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW]
22
30
30
37
37
45
45
55
55
75
Typical shaft output at 550 V [hp]
30
40
40
50
50
60
60
75
75
100
Typical shaft output at 690 V [kW]
30
37
37
45
45
55
55
75
75
90
Typical shaft output at 690 V [hp]
40
50
50
60
60
75
75
100
100
125
IP20/Chassis
B4
C3
C3
D3h
D3h
IP21/Type 1
IP55/Type 12
C2
C2
C2
C2
C2
Output current
Continuous (3x525–550 V) [A]
36
43
43
54
54
65
65
87
87
105
AJ300847815559en-000101 / 130R0337
88 | Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide