Enclosure Power [kW (hp)] Recommended
fuse size
Recommended
maximum fuse
Recommended circuit break-
er Moeller
Maximum trip
level [A]
15 (20)
gG-32
18.5 (25)
gG-40
B2
22 (30)
gG-50
gG-100
NZMB1-A100
100
30 (40)
gG-63
B3
11 (15)
gG-25
gG-63
PKZM4-50
50
15–18.5 (20–25)
gG-32
B4
22 (30)
gG-40
gG-125
NZMB1-A100
100
30 (40)
gG-50
37 (50)
gG-63
C1
37 (50)
gG-63
gG-160
NZMB2-A200
160
45 (60)
gG-100
55 (60)
aR-160
aR-250
C2
75–90 (100–125) aR-200
aR-250
NZMB2-A250
250
C3
45 (60)
gG-63
gG-150
NZMB2-A200
150
55 (75)
gG-100
C4
75 (100)
aR-160
aR-250
NZMB2-A250
250
90 (125)
aR-200
Table 71: 525–690 V, Enclosure Sizes A, B, and C
Enclosure Power [kW (hp)] Recommended fuse
size
Recommended maxi-
mum fuse
Recommended circuit
breaker Moeller
Maximum trip lev-
el [A]
A3
1.1 (1.5)
gG-6
gG-25
PKZM0-16
16
1.5 (2.0)
gG-6
gG-25
2.2 (3.0)
gG-6
gG-25
3.0 (4.0)
gG-10
gG-25
4.0 (5.0)
gG-10
gG-25
5.5 (7.5)
gG-16
gG-25
7.5 (10)
gG-16
gG-25
B2
11 (15)
gG-25
gG-63
–
–
15 (20)
gG-25
18 (24)
gG-32
22 (30)
gG-32
C2
30 (40)
gG-40
gG-80
–
–
AJ300847815559en-000101 / 130R0337
128 | Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide