Type designation
P37K
P45K
P55K
P75K
P90K
Output current
Continuous (3x380–440 V) [A]
61
73
73
90
90
106
106
147
147
177
Intermittent (60 s overload) (3x380–
440 V) [A]
91.5 80.3 110
99
135
117
159
162
221
195
Continuous (3x441–480 V) [A]
52
65
65
80
80
105
105
130
130
160
Intermittent (60 s overload) (3x441–
480 V) [A]
78
71.5 97.5 88
120
116
158
143
195
176
Continuous kVA at 400 V [kVA]
42.3 50.6 50.6 62.4 62.4 73.4
73.4
102
102
123
Continuous kVA at 460 V [kVA]
41.4 51.8 51.8 63.7 63.7 83.7
83.7
104
103.6
128
Maximum input current
Continuous (3x380–440 V) [A]
55
66
66
82
82
96
96
133
133
161
Intermittent (60 s overload) (3x380–
440 V) [A]
82.5 72.6 99
90.2 123
106
144
146
200
177
Continuous (3x441–480 V) [A]
47
59
59
73
73
95
95
118
118
145
Intermittent (60 s overload) (3x441–
480 V) [A]
70.5 64.9 88.5 80.3 110
105
143
130
177
160
Maximum pre-fuses [A]
100
125
160
250
250
Additional specifications
Protection rating IP20 maximum ca-
ble cross-section for mains and mo-
tor [mm
2
(AWG)]
35 (2)
50 (1)
50 (1)
150 (300 MCM)
150 (300 MCM)
Protection rating IP20 maximum ca-
ble cross-section for brake and load
sharing [mm
2
(AWG)]
35 (2)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
Protection ratings IP21, IP55, IP66
maximum cable cross-section for
mains and motor [mm
2
(AWG)]
50 (1)
50 (1)
50 (1)
150 (300 MCM)
150 (300 MCM)
Protection ratings IP21, IP55, IP66
maximum cable cross-section for
brake and load sharing [mm
2
(AWG)]
50 (1)
50 (1)
50 (1)
95 (4/0)
95 (4/0)
Maximum cable cross-section
(3)
for
mains disconnect [mm
2
(AWG)]
50, 35, 35 (1, 2, 2)
95, 70, 70 (3/2, 2/0,
2/0)
185, 150, 120
(350 MCM, 300 MCM,
4/0)
Estimated power loss
(4)
at rated
maximum load [W]
570
739
697
843
891
1083 1022
1384
1232
1474
AJ300847815559en-000101 / 130R0337 | 81
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202