Type designation
PK37
PK55
PK75
P1K1
P1K5
Maximum pre-fuses [A]
10
10
10
10
10
Additional specifications
Protection ratings IP20, IP21 maximum cable cross-section
(3)
for mains,
motor, brake, and load sharing [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
(minimum 0.2 (24))
Protection ratings IP55, IP66 maximum cable cross-section
(3)
for mains,
motor, brake, and load sharing [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
Maximum cable cross-section
(3)
for disconnect [mm2 (AWG)]
6, 4, 4 (10, 12, 12)
Estimated power loss
(4)
at rated maximum load [W]
(5)
35
42
46
58
62
Efficiency
(6)
0.93
0.95
0.96
0.96
0.97
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Enclosure sizes A2+A3 can be converted to IP21 using a conversion kit. See also chapters Mechanical mounting and IP21/Type 1 Enclosure kit in the
design guide.
3
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
.
5
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
. For efficiency class see
.
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
. For efficiency class see
.
Table 32: Mains Supply 3x380–480 V AC, P2K2–P7K5
Type designation
P2K2
P3K0
P4K0
P5K5
P7K5
High/normal overload
(1)
HO NO HO
NO HO
NO HO
NO
HO
NO
Typical shaft output [kW]
2.2
3.0
4.0
5.5
7.5
Typical shaft output at 460 V [hp]
2.9
4.0
5.3
7.5
10
Protection rating IP20/Chassis
(2)
A2
A2
A2
A3
A3
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
A4/A5
A4/A5
A4/A5
A5
A5
Output current
Continuous (3x380–440 V) [A]
5.6
7.2
10
13
16
Intermittent (3x380–440 V) [A]
8.4 6.2 10.8 7.9 15
11
19.5 14.3 24
17.6
Continuous (3x441–480 V) [A]
4.8
6.3
8.2
11
14.5
Intermittent (3x441–480 V) [A]
7.2 5.3 9.5
6.9 12.3 9.0 16.5 12.1 21.8 16
Continuous kVA at 400 V [kVA]
3.9
5.0
6.9
9.0
11
Continuous kVA at 460 V [kVA]
3.8
5.0
6.5
8.8
11.6
Maximum input current
Continuous (3x380–440 V) [A]
5.0
6.5
9.0
11.7
14.4
AJ300847815559en-000101 / 130R0337
78 | Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide