Enclosure Power [kW (hp)] Recommended fuse
size
Recommended maxi-
mum fuse
Recommended circuit
breaker Moeller
Maximum trip lev-
el [A]
37 (50)
gG-63
gG-100
–
–
45 (60)
gG-63
gG-125
55 (75)
gG-80
gG-160
–
–
75 (100)
gG-100
C3
37 (50)
gG-100
gG-125
–
–
45 (60)
gG-125
gG-160
–
–
10.6.3 UL Compliance
Table 72: Recommended Maximum Fuse, 1x200–240 V, Enclosure Sizes A, B, and C
Power [kW
(hp)]
Miximum
prefuse
size [A]
Bussmann
JFHR2
Bussmann
RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
1.1 (1.5)
15
FWX-15
KTN-R15
JKS-15
JJN-15
FNQ-R-15
KTK-R-15
LP-CC-15
1.5 (2.0)
20
FWX-20
KTN-R20
JKS-20
JJN-20
FNQ-R-20
KTK-R-20
LP-CC-20
2.2 (3.0)
30
FWX-30
KTN-R30
JKS-30
JJN-30
FNQ-R-30
KTK-R-30
LP-CC-30
3.0 (4.0)
35
FWX-35
KTN-R35
JKS-35
JJN-35
–
–
–
3.7 (5.0)
50
FWX-50
KTN-R50
JKS-50
JJN-50
–
–
–
5.5 (7.5)
60
FWX-60
KTN-R60
JKS-60
JJN-60
–
–
–
7.5 (10)
80
FWX-80
KTN-R80
JKS-80
JJN-80
–
–
–
15 (20)
150
FWX-150
KTN-R150
JKS-150
JJN-150
–
–
–
22 (30)
200
FWX-200
KTN-R200
JKS-200
JJN-200
–
–
–
Table 73: Recommended Maximum Fuse, 1x200–240 V, Enclosure Sizes A, B, and C
Power [kW (hp)] Maximum
Prefuse size
[A]
SIBA Type RK1 Littelfuse Type RK1 Ferraz Shaw-
mut Type CC
Ferraz Shawmut
Type RK1
(1)
Ferraz Shaw-
mut J
1.1 (1.5)
15
5017906-016
KLN-R15
ATM-R15
A2K-15R
HSJ15
1.5 (2.0)
20
5017906-020
KLN-R20
ATM-R20
A2K-20R
HSJ20
2.2 (3.0)
30
(1)
5017906-032
KLN-R30
ATM-R30
A2K-30R
HSJ30
3.0 (4.0)
35
–
KLN-R35
–
A2K-35R
HSJ35
3.7 (5.0)
50
5012406-050
KLN-R50
–
A2K-50R
HSJ50
5.5 (7.5)
60
(2)
5014006-063
KLN-R60
–
A2K-60R
HSJ60
7.5 (10)
80
5014006-080
KLN-R80
–
A2K-80R
HSJ80
15 (20)
150
5014006-150
KLN-R150
–
A2K-150R
HSJ150
AJ300847815559en-000101 / 130R0337 | 129
Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide