Type desig nation
P7K5
P11K
P18K
P37K
Continuous (1x441–480 V) [A]
30
41
72
135
Intermittent (1x441–480 V) [A]
33
46
79.2
148
Maximum pre-fuses [A]
63
80
160
250
Additional specifications
Maximum cable cross-section for mains, motor, and brake [mm
2
] (AWG)]
10 (7)
35 (2)
50 (1/0)
120 (4/0)
Estimated power loss
(1)
at rated maximum load [W]
(2)
300
440
740
1480
Efficiency
(3)
0.96
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
2
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
3
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
8.1.4 Mains Supply 3x380–480 V AC
Table 31: Mains Supply 3x380–480 V AC, PK37–P1K5
Type designation
PK37
PK55
PK75
P1K1
P1K5
High/normal overload
(1)
HO NO HO NO HO NO HO NO HO NO
Typical shaft output [kW]
0.37
0.55
0.75
1.1
1.5
Typical shaft output at 460 V [hp]
0.5
0.75
1.0
1.5
2.0
Protection rating IP20/Chassis
(2)
A2
A2
A2
A2
A2
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
Output current
Continuous (3x380–440 V) [A]
1.3
1.8
2.4
3.0
4.1
Intermittent (3x380–440 V) [A]
2.0 1.4 2.7 2.0 3.6 2.6 4.5 3.3 6.2 4.5
Continuous (3x441–480 V) [A]
1.2
1.6
2.1
2.7
3.4
Intermittent (3x441–480 V) [A]
1.8 1.3 2.4 1.8 3.2 2.3 4.1 3.0 5.1 3.7
Continuous kVA at 400 V [kVA]
0.9
1.3
1.7
2.1
2.8
Continuous kVA at 460 V [kVA]
0.9
1.3
1.7
2.4
2.7
Maximum input current
Continuous (3x380–440 V) [A]
1.2
1.6
2.2
2.7
3.7
Intermittent (3x380–440 V) [A]
1.8 1.3 2.4 1.8 3.3 2.4 4.1 3.0 5.6 4.1
Continuous (3x441–480 V) [A]
1.0
1.4
1.9
2.7
3.1
Intermittent (3x441–480 V) [A]
1.5 1.1 2.1 1.5 2.9 2.1 4.1 3.0 4.7 3.4
AJ300847815559en-000101 / 130R0337 | 77
Danfoss A/S © 2020.09
Specifications