Type designation
P2K2
P3K0
P4K0
P5K5
P7K5
Intermittent (3x380–440 V) [A]
7.5 5.5 9.8
7.2 13.5 9.9 17.6 12.9 21.6 15.8
Continuous(3x441–480 V) [A]
4.3
5.7
7.4
9.9
13
Intermittent (3x441–480 V) [A]
6.5 4.7 8.6
6.3 11.1 8.1 14.9 10.9 19.5 14.3
Maximum pre-fuses [A]
20
20
20
30
30
Additional specifications
Protection ratings IP20, IP21 maximum cable cross-section
(3)
for
mains, motor, brake, and load sharing [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
(minimum 0.2 (24))
Protection ratings IP55, IP66 maximum cable cross-section
(3)
for
mains, motor, brake, and load sharing [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
Maximum cable cross-section
(3)
for disconnect [mm
2
(AWG)]
6, 4, 4 (10, 12 ,12)
Estimated power loss
(4)
at rated maximum load [W]
(5)
88
116
124
187
225
Efficiency
(6)
0.97
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
Enclosure sizes A2+A3 can be converted to IP21 using a conversion kit. See also chapters Mechanical mounting and IP21/Type 1 Enclosure kit in the
design guide.
3
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
4
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
5
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
6
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
Table 33: Mains Supply 3x380–480 V AC, P11K–P30K
Type designation
P11K
P15K
P18K
P22K
P30K
High/normal overload
(1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output [kW]
7.5
11
11
15
15
18.5 18.5 22
22
30
Typical shaft output at 460 V [hp]
10
15
15
20
20
25
25
30
30
40
Protection rating IP20/Chassis
(2)
B3
B3
B3
B4
B4
Protection rating IP21/Type 1
B1
B1
B1
B2
B2
Protection rating IP55/Type 12
Protection rating IP66/NEMA 4X
B1
B1
B1
B2
B2
Output current
Continuous (3x380–440 V) [A]
16
24
24
32
32
37.5 37.5 44
44
61
Intermittent (60 s overload) (3x380–440 V) [A]
25.6 26.4 38.4 35.2 51.2 41.3 60
48.4 70.4 67.1
Continuous (3x441–480 V) [A]
14.5 21
21
27
27
34
34
40
40
52
Intermittent (60 s overload) (3x441–480 V) [A]
23.2 23.1 33.6 29.7 43.2 37.4 54.4 44
64
61.6
AJ300847815559en-000101 / 130R0337 | 79
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202