12 13 18 19 27 29 32 33 20 37
39
69
68
61
42 50 53 54 55
e3
0b
f1
45
.1
1
1
2
4
3
Illustration 70: Terminal Numbers on the Connectors
1
Serial communication connector
2
USB port
3
Digital input/output connector
4
Analog input/output connector
Serial communication connector provides 2 terminals (+)68 and (-) 69 for an RS485 serial communication.
USB port available for use with the MCT 10 Set-up Software.
Digital input/output connector provides:
4 programmable digital input terminals.
2 additional digital terminals programmable as either input or output.
A 24 V DC terminal supply voltage.
A common for optional customer-supplied 24 V DC voltage.
Analog input/output connector provides:
2 analog inputs.
1 analog output.
10 V DC supply voltage.
Commons for the inputs and output.
10.5.4 Terminal Descriptions
Table 63: Digital Inputs/Outputs
Terminal Parameter
Default setting
Description
12, 13
–
+24 V DC
+24 V DC supply voltage for digital inputs and ex-
ternal transducers. Maximum output current
200 mA for all 24 V loads.
18
Parameter 5-10 Terminal 18 Digital In-
puts
[8] Start
Digital inputs
19
Parameter 5-11 Terminal 19 Digital In-
puts
[0] No operation
32
Parameter 5-14 Terminal 32 Digital Input [0] No operation
33
Parameter 5-15 Terminal 33 Digital Input [0] No operation
27
Parameter 5-12 Terminal 27 Digital Input [2] Coast inverse
For digital input or output. Default setting is input.
29
Parameter Terminal 29 Digital Input
[14] Jog
20
–
–
Common for digital inputs and 0 V potential for
24 V supply.
37
–
Safe Torque Off (STO) Safe input (optional). Used for STO.
AJ300847815559en-000101 / 130R0337
124 | Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide