Power [kW (hp)]
Bussmann Type
RK1
(1)
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
15 (20)
KTN-R80
JKS-80
JJN-80
–
–
–
18.5–22 (25–30)
KTN-R125
JKS-125
JJN-125
–
–
–
30 (40)
KTN-R150
JKS-150
JJN-150
–
–
–
37 (50)
KTN-R200
JKS-200
JJN-200
–
–
–
45 (60)
KTN-R250
JKS-250
JJN-250
–
–
–
1
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
Table 77: Recommended Maximum Fuse, 3x220–240 V, Enclosure Sizes A, B, and C
Power [kW
(hp)]
SIBA Type RK1 Littelfuse
Type RK1
Ferraz-
Shawmut
Type CC
Ferraz- Shaw-
mut Type
RK1
(1)
Bussmann
Type
JFHR2
(2)
Littelfuse
JFHR2
Ferraz-
Shawmut
JFHR2
(3)
Ferraz-
Shawmut
J
0.25–0.37
(0.34–0.5)
5017906-005
KLN-R-05
ATM-R-05
A2K-05-R
FWX-5
–
–
HSJ-6
0.55–1.1
(0.75–1.5)
5017906-010
KLN-R-10
ATM-R-10
A2K-10-R
FWX-10
–
–
HSJ-10
1.5 (2.0)
5017906-016
KLN-R-15
ATM-R-15
A2K-15-R
FWX-15
–
–
HSJ-15
2.2 (3.0)
5017906-020
KLN-R-20
ATM-R-20
A2K-20-R
FWX-20
–
–
HSJ-20
3.0 (4.0)
5017906-025
KLN-R-25
ATM-R-25
A2K-25-R
FWX-25
–
–
HSJ-25
3.7 (4.0)
5012406-032
KLN-R-30
ATM-R-30
A2K-30-R
FWX-30
–
–
HSJ-30
5.5–7.5
(7.5–10)
5014006-050
KLN-R-50
–
A2K-50-R
FWX-50
–
–
HSJ-50
11 (15)
5014006-063
KLN-R-60
–
A2K-60-R
FWX-60
–
–
HSJ-60
15 (20)
5014006-080
KLN-R-80
–
A2K-80-R
FWX-80
–
–
HSJ-80
18.5–22
(25–30)
2028220-125
KLN-
R-125
–
A2K-125-R
FWX-125
–
–
HSJ-125
30 (40)
2028220-150
KLN-
R-150
–
A2K-150-R
FWX-150
L25S-150
A25X-150
HSJ-150
37 (50)
2028220-200
KLN-
R-200
–
A2K-200-R
FWX-200
L25S-200
A25X-200
HSJ-200
45 (60)
2028220-250
KLN-
R-250
–
A2K-250-R
FWX-250
L25S-250
A25X-250
HSJ-250
1
A6KR fuses from Ferraz-Shawmut may substitute A2KR for 240 V drives.
2
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
3
A50X fuses from Ferraz-Shawmut may substitute A25X for 240 V drives.
Table 78: Recommended Maximum Fuse, 3x380–480 V, Enclosure Sizes A, B, and C
Power [kW (hp)] Bussmann Type
RK1
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
–
KTS-R-6
JKS-6
JJS-6
FNQ-R-6
KTK-R-5
LP-CC-5
AJ300847815559en-000101 / 130R0337 | 131
Danfoss A/S © 2020.09
Electrical Installation
Considerations
VLT® AQUA Drive FC 202
Design Guide