Type designation
P1K1
P1K5
P2K2
P3K0
P4K0
P5K5
P7K5
Intermittent (3x551–690 V) [A]
2.4 1.8 3.3 2.4 4.8 3.5 6.8 5.0 8.3 6.1 11.3 8.3 15
11
Continuous kVA at 525 V [kVA]
1.9
2.5
3.5
4.5
5.5
8.2
10
Continuous kVA at 690 V [kVA]
1.9
2.6
3.8
5.4
6.6
9.0
12
Maximum input current
Continuous (3x525–550 V) [A]
1.9
2.4
3.5
4.4
5.5
8.1
9.9
Intermittent (3x525–550 V) [A]
2.9 2.1 3.6 2.6 5.3 3.9 6.6 4.8 8.3 6.1 12.2 8.9 14.9 10.9
Continuous (3x551–690 V) [A]
1.4
2.0
2.9
4.0
4.9
6.7
9.0
Intermittent (3x551–690 V) [A]
2.1 1.5 3.0 2.2 4.4 3.2 6.0 4.4 7.4 5.4 10.1 7.4 13.5 9.9
Additional specifications
Maximum cable cross–section
(2)
for mains,
motor, brake, and load sharing [mm
2
(AWG)]
4, 4, 4 (12, 12, 12)
(minimum (24))
Maximum cable cross–section
(2)
for mains
disconnect [mm
2
(AWG)]
6, 4, 4 (10, 12, 12)
Estimated power loss
(3)
at rated maximum
load [W]
(4)
44
60
88
120
160
220
300
Efficiency
(5)
0.96
1
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110% torque for a duration of 60 s.
2
The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
3
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to
mydrive ecosmart on
. For efficiency class see
4
Efficiency measured at nominal current. For more detailed efficiency values and part load losses according IEC/EN 61800-9-2 refer to mydrive ecos-
mart on
5
Measured using 5 m (16 ft) shielded motor cables at rated load and rated frequency. For more detailed efficiency values and part load losses ac-
cording IEC/EN 61800-9-2 refer to mydrive ecosmart on
Table 40: Enclosure, Mains Supply 3x525–690 V AC IP20/IP21/IP55 – Chassis/Type 1/Type 12, P11K–P30K Specifications VLT® AQUA Drive FC 202
Type designation
P11K
P15K
P18K
P22K
P30K
High/normal overload
(1)
HO
NO
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW]
5.9
7.5
7.5
11
11
15
15
18.5 18.5 22
Typical shaft output at 550 V [hp]
7.5
10
10
15
15
20
20
25
25
30
Typical shaft output at 690 V [kW]
7.5
11
11
15
15
18.5 18.5 22
22
30
Typical shaft output at 690 V [hp]
10
15
15
20
20
25
25
30
30
40
IP20/Chassis
B4
B4
B4
B4
B4
IP21/IP55, Type 1/Type 12
B2
B2
B2
B2
B2
Output current
Continuous (3x525–550 V) [A]
11
14
14
19
19
23
23
28
28
36
Intermittent (60 s overload) (3x525–550 V) [A]
17.6 15.4 22.4 20.9 30.4 25.3 36.8 30.8 44.8 39.6
AJ300847815559en-000101 / 130R0337 | 87
Danfoss A/S © 2020.09
Specifications
VLT® AQUA Drive FC 202
Design Guide