8-03 Control Word Timeout Time
Range:
Function:
out. The timeout counter is triggered by
a valid control word.
8-04 Control Word Timeout Function
Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
specified in
8-03 Control Word Timeout Time
.
Option:
Function:
[0]
*
Off
Resumes control via serial bus (Serial
communication bus or standard) using the
most recent control word.
[1]
Freeze output Freezes output frequency until communi-
cation resumes.
[2]
Stop
Stops with auto-restart when communi-
cation resumes.
[3]
Jogging
Runs the motor at JOG frequency until
communication resumes.
[4]
Max. speed
Runs the motor at maximum frequency
until communication resumes.
[5]
Stop and trip Stops the motor, then resets the unit in
order to restart: via the Serial
communication bus, via the reset button on
the LCP or via a digital input.
[7]
Select setup 1 Changes the set-up upon reestablishment of
communication following a control word
timeout. If communication resumes causing
the timeout situation to disappear,
defines
whether to resume the set-up used before
the timeout or to retain the set-up
endorsed by the timeout function.
[8]
Select setup 2 See [7]
Select set-up 1
[9]
Select setup 3 See [7]
Select set-up 1
[10] Select setup 4 See [7]
Select set-up 1
NOTE!
The following configuration is required in order to change
the set-up after a timeout:
Set
to [9]
Multi set-up
and select the
relevant link in
8-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid
control word following a timeout. This
parameter is active only when
8-04 Control
Timeout Function
is set to [Set-up 1-4].
8-05 End-of-Timeout Function
Option:
Function:
[0]
Hold set-up
Retains the set-up selected in
8-04 Control
Timeout Function
and displays a warning,
until
8-06 Reset Control Timeout
toggles. Then
the unit resumes its original set-up.
[1]
*
Resume set-
up
Resumes the set-up active prior to the
timeout.
8-06 Reset Control Word Timeout
This parameter is active only when
Hold set-up
[0] has been
selected in
.
Option:
Function:
[0]
*
Do not reset Retains the set-up specified in
8-04 Control
Word Timeout Function
, following a control
word timeout.
[1]
Do reset
Returns the unit to the original set-up
following a control word timeout. The unit
performs the reset and then immediately
reverts to the
Do not reset
[0] setting
6.5.2 8-3* FC Port Settings
8-30 Protocol
Option:
Function:
[0]
*
FC
Communication according to the FC Protocol
as described in the
VLT AutomationDrive
Design Guide, RS485 Installation and Set-up
.
[1]
FC MC
Select the protocol for the FC (standard) port.
[2]
*
Modbus RTU
8-31 Address
Range:
Function:
Application dependent
*
[Application dependant]
8-32 FC Port Baud Rate
Option:
Function:
[0]
2400 Baud
Baud rate selection for the FC (standard)
port.
[1]
4800 Baud
[2]
*
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
How to Program
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6-15
6
6
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...