No.
Description
Warning
Alarm/Trip
Alarm/Trip Lock
Parameter Reference
39
Heatsink sensor
X
X
40
Overload of Digital Output Terminal 27
(X)
5-00, 5-01
41
Overload of Digital Output Terminal 29
(X)
5-00, 5-02
46
Pwr. card supply
X
X
47
24 V supply low
X
X
X
48
1.8 V supply low
X
X
65
Control Board Over-temperature
X
X
X
66
Heat sink Temperature Low
X
67
Option Configuration has Changed
X
68
Safe Stop Activated
X
1)
69
Pwr. Card Temp
X
X
70
Illegal FC configuration
X
72
Dangerous Failure
X
1)
73
Safe Stop Auto Restart
76
Power Unit Set-up
X
79
Illegal PS config
X
X
80
Drive Initialized to Default Value
X
244
Heatsink temp
X
X
X
245
Heatsink sensor
X
X
246
Pwr.card supply
X
X
247
Pwr.card temp
X
X
248
Illegal PS config
X
X
250
New spare part
X
251
New type code
X
X
300
Line Power Cont. fault
X
301
SC Cont. Fault
X
302
Cap. Overcurrent
X
X
303
Cap. Earth Fault
X
X
304
DC Overcurrent
X
X
305
Line Power Freq. Limit
X
308
Resistor temp
X
X
309
Line Power Ground Fault
X
X
311
Switch. Freq. Limit
X
314
Auto CT Interrupt
X
315
Auto CT Error
X
316
CT Location Error
X
317
CT Polarity Error
X
318
CT Ratio Error
X
Table 9.1 Alarm/Warning code list
A trip is the action when an alarm has appeared. The trip
will stop the filter operation and can be reset by pressing
the reset button or make a reset by a digital input (Par.
5-1* [1]). The origin event that caused an alarm cannot
damage the filter or cause dangerous conditions. A trip
lock is an action when an alarm occurs, which may cause
damage to the device or connected parts. A trip lock
situation can only be reset by power cycling.
LED indication
Warning
yellow
Alarm
flashing red
Trip locked
yellow and red
Troubleshooting
VLT Active Filter AAF 00x
9-2
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
9
9
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...