6.7 15-0* Operating Data
Parameter group containing filter information such as
operating data, hardware configuration and software
versions.
6.7.1 15-0* Operating Data
15-00 Operating Hours
Range:
Function:
0 h
*
[0 - 2147483647 h] View how many hours the unit has
run. The value is saved when the unit
is turned off.
15-01 Running Hours
Range:
Function:
0 h
*
[0 - 2147483647
h]
View how many hours the filter has
run. Reset the counter in
15-07 Reset
Running Hours Counter
. The value is
saved when the unit is turned off.
15-03 Power-ups
Range:
Function:
0
*
[0 - 2147483647 ] View the number of times the unit has
been powered up.
15-04 Over Temps
Range:
Function:
0
*
[0 - 65535 ] View the number of unit temperature faults
which have occurred.
15-05 Over Volts
Range:
Function:
0
*
[0 - 65535 ] View the number of unit overvoltages which
have occurred.
15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not reset
[1]
Reset counter Select
Reset
[1] and press [OK] to reset the
Running Hours counter to zero (see
). This parameter cannot
be selected via the serial port, RS-485.
Select
Do not reset
[0] if no reset of the
Running Hours counter is desired.
6.7.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources (
15-10 Logging Source
) at individual rates
(
). A trigger event (
15-12 Trigger
Event
) and window (
15-14 Samples Before Trigger
) are used
to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
Function:
Select which variables are to be
logged.
[0]
*
None
[1600] Control Word
[1603] Status Word
[1630] DC Link Voltage
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1660] Digital Input
[1666] Digital Output [bin]
[1690] Alarm Word
[1692] Warning Word
[1694] Ext. Status Word
15-11 Logging Interval
Range:
Function:
Application
dependent
*
[Application
dependant]
Enter the interval in
milliseconds between each
sampling of the variables to
be logged.
15-12 Trigger Event
Select the trigger event. When the trigger event occurs, a
window is applied to freeze the log. The log will then retain a
specified percentage of samples before the occurrence of the
trigger event (
).
Option:
Function:
[0]
*
False
[1]
True
[2]
Running
[6]
Current limit
[16]
Thermal warning
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
How to Program
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6-19
6
6
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...