5-10 Terminal 18 Digital Input
Option:
Function:
[100] Follower AF
#2 Run
Feedback
Do not program this setting. It is done
automatically for paralleling. See
300-40 Master Follower Selection
and
for more infomation
about paralleling.
[101] Sleep
The filter goes into sleep mode at light
duty to save energy.
5-11 Terminal 19 Digital Input
Option:
Function:
[0]
*
No Operation Functions are described under 5-1*
Digital
Inputs
5-12 Terminal 27 Digital Input
Option:
Function:
[0]
*
No Operation Functions are described under 5-1*
Digital
Inputs
5-13 Terminal 29 Digital Input
Option:
Function:
[0]
*
No Operation Functions are described under 5-1*
Digital
Inputs
5-14 Terminal 32 Digital Input
Option:
Function:
[90]
*
AC Contactor Functions are described under 5-1*
Digital
Inputs
5-15 Terminal 33 Digital Input
Option:
Function:
[91]
*
DC Contactor Functions are described under 5-1*
Digital
Inputs
5-16 Terminal X30/2 Digital Input
Option:
Function:
[0]
*
No operation Functions are described under 5-1*
Digital
Inputs
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0]
*
No operation Functions are described under 5-1*
Digital
Inputs
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0]
*
No operation Functions are described under 5-1*
Digital
Inputs
5-19 Terminal 37 Safe Stop
Option:
Function:
[1]
*
Safe Stop
Alarm
Coasts unit when safe stop is activated.
Manual reset from LCP, digital input or Serial
communication bus.
[3]
Safe Stop
Warning
Coasts unit when safe stop is activated (T-37
off). When safe stop circuit is reestablished,
the unit will continue without manual reset.
[4]
PTC 1
Alarm
Coasts unit when safe stop is activated.
Manual reset from LCP, digital input or Serial
communication bus. Choice 4 is only available
when the MCB 112 PTC thermistor card is
connected.
[5]
PTC 1
Warning
Coasts unit when safe stop is activated (T-37
off). When safe stop circuit is reestablished,
the unit will continue without manual reset,
unless a digital input set to PTC Card 1 [80] is
still enabled. Choice 5 is only available when
the MCB 112 PTC thermistor card is
connected.
[6]
PTC 1 &
Relay A
This choice is used when the PTC option is
gated together with a stop button through a
safety relay to T-37. Coasts unit when safe
stop is activated. Manual reset from LCP,
digital input or Serial communication bus.
Choice 6 is only available when the MCB 112
PTC thermistor card is connected.
[7]
PTC 1 &
Relay W
This choice is used when the PTC option is
gated together with a stop button through a
safety relay to T-37. Coasts unit when safe
stop is activated (T-37 off). When safe stop
circuit is reestablished, the unit will continue
without manual reset, unless a digital input
set to PTC Card 1 [80] is (still) enabled. Choice
7 is only available when the MCB 112 PTC
thermistor card is connected.
[8]
PTC 1 &
Relay A/W
This choice makes it possible to use a
combination of alarm and warning. Choice 8
is only available when the MCB 112 PTC
thermistor card is connected.
[9]
PTC 1 &
Relay W/A
This choice makes it possible to use a
combination of alarm and warning. Choice 9
is only available when the MCB 112 PTC
thermistor card is connected.
Choices 4–9 are only available when the MCB 112 PTC
thermistor card is connected.
How to Program
VLT Active Filter AAF 00x
6-12
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6
6
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...