Under [Quick Menu] and [Changes Made], any
parameter that has been changed from factory
settings is displayed.
•
Press and hold the [Main Menu] key for 3
seconds to access any parameter
•
For service purposes, it is recommended to copy
all of the parameters to the LCP; see
for further information.
5.1.7 Quick Transfer of Parameter Settings
between Multiple Active Filters
Once the set-up of a filter is complete, we recommend
that you store the data in the LCP or on a PC via MCT 10
Set-up Software.
Data storage in LCP:
1.
Go to
0-50 LCP Copy
2.
Press the [OK] key
3.
Select “All to LCP”
4.
Press the [OK] key
All parameter settings are now stored in the LCP indicated
by the progress bar. When 100% is reached, press [OK].
You can now connect the LCP to another filter and copy
the parameter settings to this unit as well.
Data transfer from LCP to filter:
1.
Go to
0-50 LCP Copy
2.
Press the [OK] key
3.
Select “All from LCP”
4.
Press the [OK] key
The parameter settings stored in the LCP are now
transferred to the filter indicated by the progress bar.
When 100% is reached, press [OK].
5.1.8 Initialization to Default Settings
There are two ways to initialize the filter to default:
recommended initialization and manual initialization.
Please be aware that they have different impact according
to the description below.
Recommended initialization (via
14-22 Operation Mode
)
1.
Select
14-22 Operation Mode
2.
Press [OK]
3.
Select “Initialization” (for NLCP select “2”)
4.
Press [OK]
5.
Disconnect the power from the unit and wait for
the display to turn off.
6.
Reconnect power and the unit is reset. Note that
first start-up takes a few more seconds
7.
Press [Reset]
14-22 Operation Mode
initializes all except:
14-50 RFI 1
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Maximum Inter-Char Delay
15-00 Operating Hours
to
to
15-30 Alarm Log: Error Code
to
NOTE!
Parameters selected in
0-25 My Personal Menu
will remain
present with the default factory setting.
Manual initialization
NOTE!
When carrying out manual initialization, serial communi-
cation and fault log settings are reset.
1. Disconnect from the line power and wait until
the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the
same time while powering up for LCP
2b. Press [Menu] while powering up for LCP 101,
Numerical Display
3. Release the keys after 5 secs
4. The active filter is now programmed according
to default settings
This parameter initializes all except:
15-00 Operating Hours
15-03 Power-ups
15-04 Over Temps
15-05 Over Volts
5.1.9 RS-485 Bus Connection
The filter can be connected to a controller (or master)
together with other loads using the RS-485 standard
interface. Terminal 68 is connected to the P signal (TX+, RX
+), while terminal 69 is connected to the N signal (TX-,RX-).
How to Operate the Active F...
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
5-5
5
5
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...