15-13 Logging Mode
Option:
Function:
[0]
*
Log always
Select
Log always
[0] for continuous
logging.
[1]
Log once on
trigger
Select
Log once on trigger
[1] to
conditionally start and stop logging using
15-12 Trigger Event
and
15-14 Samples
Before Trigger
.
15-14 Samples Before Trigger
Range:
Function:
50
*
[0 - 100 ] Enter the percentage of all samples prior to a
trigger event which are to be retained in the
log. See also
15-12 Trigger Event
and
6.7.3 15-2* Historic Log
View up to 50 logged data items via the array parameters
in this parameter group. For all parameters in the group,
[0] is the most recent data and [49] the oldest data. Data is
logged every time an
event
occurs (not to be confused
with SLC events).
Events
in this context are defined as a
change in one of the following areas:
1.
Digital input
2.
Digital outputs (not monitored in this SW release)
3.
Warning word
4.
Alarm word
5.
Status word
6.
Control word
7.
Extended status word
Events
are logged with value, and time stamp in msec. The
time interval between two events depends on how often
events
occur (maximum once every scan time). Data
logging is continuous but if an alarm occurs, the log is
saved and the values can be viewed on the display. This
feature is useful, for example when carrying out service
following a trip. View the historic log contained in this
parameter via the serial communication port or via the
display.
15-20 Historic Log: Event
Array [50]
Range:
Function:
0
*
[0 - 255 ]
View the event type of the logged events.
15-21 Historic Log: Value
Array [50]
Range:
Function:
0
*
[0 -
2147483647 ]
View the value of the logged event.
Interpret the event values according to this
table:
Digital input
Decimal value. See
for
description after
converting to binary
value.
Digital output
(not
monitored in
this SW
release)
Decimal value. See
for description after
converting to binary
value.
Warning word Decimal value. See
16-92 Warning Word
for
description.
Alarm word
Decimal value. See
16-90 Alarm Word
for
description.
Status word
Decimal value. See
for
description after
converting to binary
value.
Control word
Decimal value. See
for
description.
Extended
status word
Decimal value. See
for
description.
15-22 Historic Log: Time
Array [50]
Range:
Function:
0 ms
*
[0 - 2147483647
ms]
View the time at which the logged
event occurred. Time is measured in
ms since unit start. The max. value
corresponds to approx. 24 days which
means that the count will restart at
zero after this time period.
6.7.4 15-3* Alarm Log
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Error codes, values and time
stamp can be viewed for all logged data.
How to Program
VLT Active Filter AAF 00x
6-20
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6
6
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...