Overview of functions, alarms and warnings
Function
No.
PTC
Relay
No Function
[0]
-
-
Safe Stop
Alarm
[1]*
-
Safe Stop [A68]
Safe Stop
Warning
[3]
-
Safe Stop [W68]
PTC 1 Alarm
[4]
PTC 1 Safe Stop
[A71]
-
PTC 1 Warning [5]
PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay
A
[6]
PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay
W
[7]
PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay
A/W
[8]
PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay
W/A
[9]
PTC 1 Safe Stop
[W71]
Safe Stop [A68]
W means warning, and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or the Instruction Manual.
A dangerous failure related to the safe stop will give alarm:
Dangerous Failure [A72].
Please refer to the section
Description of Alarm Word,
Warning Word and extended Status Word
in the chapter
Troubleshooting
.
6.4.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in
, and set the I/O
function for terminal 29 in
. These
parameters cannot be adjusted while the unit is running.
5-30 Terminal 27 Digital Output
Option:
Function:
[0]
No operation
Default for all digital outputs and relay
outputs
[1]
Control ready
The control card is ready. For example,
Feedback from a Adjustable frequency
drive where the control is supplied by an
external 24 V (MCB 107) and the main
power to Adjustable frequency drive is
not detected.
[2]
Unit ready
The unit is ready for operation and
applies a supply signal on the control
board.
5-30 Terminal 27 Digital Output
Option:
Function:
[4]
Enable / no
warning
Ready for operation. No start or stop
command is been given (start/disable). No
warnings are active.
[5]
Running
Motor is running and shaft torque is
present.
[9]
Alarm
An alarm activates the output. There are
no warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[12]
Current limit
The motor current is outside the range
set in
4-18 Current Limit
.
[21]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the unit, the brake resistor or the
thermistor.
[22]
Ready,no
thermal W
unit is ready for operation and there is no
overtemperature warning.
[24]
Ready, voltage
OK
unit is ready for operation and the AC
line voltage is within the specified voltage
range (see
General Specifications
section in
the Design Guide).
[26]
Bus OK
Active communication (no timeout) via
the serial communication port.
[55]
Pulse output
[122] No alarm
[125] Hand mode
Output is high when the unit is in hand
on mode (as indicated by the LED light
above [Hand on]).
[126] Auto mode
[152] AF sleeping
5-31 Terminal 29 Digital Output
Option:
Function:
[0]
*
No operation Functions are described under 5-3*
Digital
Outputs
This parameter only applies to FC 302
6.4.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Option:
Function:
[0]
No operation
[128]
SC contactor
[129]
Mains contactor
How to Program
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6-13
6
6
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...