The connector located on the power card provides the AC
line voltage connection for the cooling fans. The fans are
factory-equipped to be supplied from a common AC line
(jumpers between 100-102 and 101-103). If an external
supply is needed, the jumpers are removed and the supply
is connected to terminals 100 and 101. A 5 Amp fuse
should be used for protection. In UL applications this
should be LittelFuse KLK-5 or equivalent.
How to Install
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
4-31
4
4