0-42 [Auto on] Key on LCP
Option:
Function:
[0]
*
Disabled Avoid accidental start of the unit in auto mode.
[1]
*
Enabled
[2]
Password Avoids unauthorized start in auto mode. If
is included in the
Quick Menu, then define the password in
0-43 [Reset] Key on LCP
Option:
Function:
[0]
*
Disabled
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1]
*
Enabled
[2]
Password
Avoids unauthorized resetting. If
is included in the
Quick Menu, then define the password in
.
[7]
Enabled
without OFF
Resets the Adjustable frequency drive
without setting it in
Off
mode.
[8]
Password
without OFF
Resets the Adjustable frequency drive
without setting it in
Off
mode. A password
is required when pressing [Reset] (see [2]).
6.3.7 0-5* Copy/Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups
from the filter memory to the LCP
memory.
[2]
All from LCP
Copies all parameters in all set-ups
from the LCP memory to the filter
memory.
[3]
Size indep. from
LCP
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to
program several filters with the same
function without disturbing motor
data.
[4]
File from MCO to
LCP
[5]
File from LCP to
MCO
[6]
Data from DYN to
LCP
0-50 LCP Copy
Option:
Function:
[7]
Data from LCP to
DYN
This parameter cannot be adjusted while the motor is
running.
0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function
[1]
Copy to set-
up 1
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 1.
[2]
Copy to set-
up 2
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 2.
[3]
Copy to set-
up 3
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 3.
[4]
Copy to set-
up 4
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up
) to Set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up
over to each of the set-ups 1 to 4.
6.3.8 0-6* Password
0-60 Main Menu Password
Range:
Function:
100
*
[0 - 999 ] Define the password for access to the main
menu via the [Main Menu] key. If
0-61 Access to
Main Menu w/o Password
is set to
Full access
[0], this parameter will be ignored.
How to Program
VLT Active Filter AAF 00x
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6-9
6
6
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...