5-41 On Delay, Relay
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 - 600.00 s] Enter the delay of the relay cut-in
time. Select one of available
mechanical relays and MCB 105 in an
array function. See
5-40 Function Relay
.
Relay 3-6 are included in MCB 113.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
5-42 Off Delay, Relay
Array [9] (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Range:
Function:
0.01 s
*
[0.01 - 600.00 s] Enter the delay of the relay cut-out
time. Select one of available
mechanical relays and MCB 105 in an
array function. See
5-40 Function Relay
.
Selected
Event
Relay
output
On Delay
P 5-41
Off Delay
P 5-42
130BA172.10
If the selected event condition changes before the on or
off delay timer expires, the relay output is unaffected.
6.5 8-** General Settings
6.5.1 8-0* General Settings
8-01 Control Site
Option:
Function:
The setting in this parameter overrides
the settings in
8-50 Coasting Select
to
8-56 Preset Reference Select
.
[0]
*
Digital and ctrl.
word
Control by using both digital input and
control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Control word
only
Control by using control word only.
8-02 Control Word Source
Select the source of the control word: one of two serial interfaces
or four installed options. During initial power-up, the unit
automatically sets this parameter to
Option A
[3] if it detects a
valid Serial communication bus option installed in slot A. If the
option is removed, the unit detects a change in the configu-
ration, sets
back to default setting
FC
RS-485, and the unit then trips. If an option is installed after
initial power-up, the setting of
will not
change but the unit will trip and display: Alarm 67
Option
Changed
.
When you retrofit a bus option into a Adjustable frequency drive
that did not have a bus option installed to begin with, you must
take an ACTIVE decision to move the control to bus-based. This
is done for safety reasons in order to avoid an accidental change.
This parameter cannot be adjusted while the motor is running.
Option:
Function:
[0]
None
[1]
FC RS485
[2]
FC USB
[3]
*
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
[30]
External Can
8-03 Control Word Timeout Time
Range:
Function:
1.0 s
*
[Application
dependant]
Enter the maximum time expected to
pass between the reception of two
consecutive messages. If this time is
exceeded, it indicates that the serial
communication has stopped. The
function selected in
8-04 Control Word
Timeout Function
will then be carried
How to Program
VLT Active Filter AAF 00x
6-14
MG.90.V2.22 - VLT
®
is a registered Danfoss trademark
6
6
Содержание VLT AAF00x
Страница 1: ...MAKING MODERN LIVING POSSIBLE VLT Active Filter AAF00x Instruction Manual...
Страница 5: ...Contents VLT Active Filter AAF 00x MG 90 V2 22 VLT is a registered Danfoss trademark...
Страница 13: ...Introduction to VLT Active VLT Active Filter AAF 00x 3 4 MG 90 V2 22 VLT is a registered Danfoss trademark 3 3...
Страница 59: ...How to Operate the Active F VLT Active Filter AAF 00x 5 8 MG 90 V2 22 VLT is a registered Danfoss trademark 5 5...
Страница 95: ...How to Program VLT Active Filter AAF 00x 6 36 MG 90 V2 22 VLT is a registered Danfoss trademark 6 6...
Страница 103: ...RS 485 Installation and set VLT Active Filter AAF 00x 7 8 MG 90 V2 22 VLT is a registered Danfoss trademark 7 7...
Страница 117: ...www danfoss com drives MG90V222 130R0506 MG90V222 Rev 2011 06 17...