background image

RAVEN Studio Sprinklers 

5.6K Pendent and Horizontal Sidewall 

Quick Response, Standard and Extended Coverage

Page 1 of 16 

AUGUST 2018 

TFP658

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

TYCO RAVEN Studio Sprinklers 5.6K 

Pendent and Horizontal Sidewall (HSW) 

Quick Response, Standard Coverage 

for Light and Ordinary Hazard applica-

tions and Extended Coverage for Light 

Hazard applications only, are intended 

for use in areas as designed per NFPA 

13.
The flush design is made aesthetically 

appealing by concealing the deflec-

tor and other operating parts behind 

the link assembly. The RAVEN Studio 

Sprinklers, with a heat sensitive solder 

type release element, are listed as  

quick response sprinklers.

NOTICE

RAVEN Studio Sprinklers described 

herein must be installed and main-

tained in compliance with this docu-

ment and with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (NFPA), in addition to 

the standards of any authorities having 

jurisdiction. Failure to do so may impair 

the performance of these devices.
Johnson Controls specifically dis-

claims any liability for damages or 

injury (including death) arising out of 

or caused by manipulation, disman-

tling, or misuse of RAVEN Studio Sprin-

klers or the use or attempted use of the 

RAVEN Studio Sprinklers or any com-

ponent thereof as an instrument unre-

lated to its intended function as a fire 

protection device.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Numbers (SINs)

Standard Coverage

TY1281 – Pendent 

TY1381 – Horizontal Sidewall

Extended Coverage

TY1282 – Pendent 

TY1382 – Horizontal Sidewall

Technical 

Data

Approvals

UL and C-UL Listed

Maximum Working Pressure

175 psi (12,1 bar)

Thread Connection

Adapter: 1/2 in. NPT x ISO 228 G3/8 in. 

Sprinkler: ISO 228 G3/8 in.

Note:

 Threads per ISO 228 are parallel 

pipe threads.

Discharge Coefficient

K=5.6 gpm/psi

1/2 

(80,6 lpm/bar

1/2

)

Temperature Rating

165°F (74°C)

Finishes

Sprinkler: White, Grey, or Custom Color
Escutcheon: White, Grey, Chrome, 

Primed*, Custom Color, or Electropolish**

(Refer to Ordering Procedure for details.)

* Ready to paint-in-place
** Chrome-coated appearance, available for Stainless 
Steel only

Physical Characteristics

Body . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass 

Deflector Assembly  . . . . . . . . . . . . . . . . . Bronze 

Sealing Assembly . Beryllium Nickel w/TEFLON 

Link Assembly  . . . . . . . . . . . . . . . . . . . . . Copper 

Thread Adapter  . . . . . . . . . . . . . . . . . . . . . Brass 

Escutcheon  . . . . . . . . Carbon or Stainless Steel

Содержание tyco RAVEN

Страница 1: ...CIATION NFPA in addition to the standards of any authorities having jurisdiction Failure to do so may impair the performance of these devices Johnson Controls specifically dis claims any liability for damages or injury including death arising out of or caused by manipulation disman tling or misuse of RAVEN Studio Sprin klers or the use or attempted use of the RAVEN Studio Sprinklers or any com pon...

Страница 2: ...AL SIDEWALL SHOWN LINK ASSEMBLY FACTORY PAINTED AREA EXPOSED BRASS SHOULDER BODY A INSTALLATION LIP BASE FLANGE CLEARANCE HOLE C B A PRONGS Application Coverage SIN Dust Cap Color A Inches mm Pendent Standard TY1281 Red 1 7 8 48 Extended TY1282 Horizontal Sidewall Standard TY1381 Green 2 13 16 56 Extended TY1382 Dimensions Inches mm Dim Escutcheon Style J K A Dia 3 76 4 101 B 7 16 11 C Dia Min 2 5...

Страница 3: ...THREADS OF CPVC SPRINKLER ADAPTER FITTING THREAD ADAPTER NOT REQUIRED REFER TO CPVC INSTALLATION HANDBOOK IH 1900 FOR GUIDANCE ON INSTALLING FITTINGS IN CPVC PIPE SYSTEMS CPVC SPRINKLER ADAPTER FITTINGS WITH ISO 228 G3 8 OUTLET THREADS DESIGNED FOR USE IN LOW PROFILE LIMITED SPACE INSTALLATIONS 90 ELBOW TEE D Y C C X Y D A A B E C X X B A Fitting Type A Nominal Pipe Size Inches DN B Outlet Thread ...

Страница 4: ...ING FACE OF THREAD ADAPTER SPRINKLER FITTING AND WATERWAY CENETRLINE STYLE J OR K ESCUTCHEON CEILING OR WALL ESCUTCHEON MOUNTING SURFACE CLEARANCE HOLE CEILING OR WALL COVERING MATERIAL FACE OF FRAMING MEMBER SPRINKLER BODY ENGAGED BY ESCUTCHEON PRONGS A B SPRINKLER FITTING THREAD ADAPTER Thread Adapter Size Thread Adapter Length Inches mm A Inches mm B Nominal Inches mm Pendent Horizontal Sidewal...

Страница 5: ...TYLE J OR K ESCUTCHEON CEILING OR WALL ESCUTCHEON MOUNTING SURFACE CLEARANCE HOLE CEILING OR WALL COVERING MATERIAL FACE OF FRAMING MEMBER SPRINKLER BODY ENGAGED BY ESCUTCHEON PRONGS A CPVC PIPE FROM SYSTEM CPVC SPRINKLER ADAPTER FITTING WITH ISO 228 G3 8 OUTLET THREADS REF FIGURE 4 Fitting Type Fitting Size Inches x ISO 228 Outlet Threads A Inches mm Pendent Horizontal Sidewall Min Max Min Max 90...

Страница 6: ...ION AND REMOVAL CAP PRONGS UNIQUELY SPACED TO ENGAGE SPRINKLER WRENCHING NOTCHES RAVEN STUDIO SPRINKLER UP INDICATES TOP OF HORIZONTAL SIDEWALL SPRINKLER DEFLECTOR CAP FLAT ACCOMMODATES LEVEL IF NECESSARY FOR HORIZONTAL SIDEWALL SPRINKLER INSTALLATION CENTER MARKING POINT FINGER GRIP CAP IS FOR SINGLE USE ONLY DO NOT RE USE AFTER PAINTING USE CAP FOR SPRINKLER INSTALLATION AND PROTECTION WHILE PAI...

Страница 7: ... SYSTEM APPLY SEALANT AROUND FIRST 2 3 MINIMUM SPRINKLER INLET THREADS NOTES 3 1 ALLOW MINIMUM 1 HOUR CURE TIME BEFORE SYSTEM PRESSURE TESTING REFER TO LOCTITE 243 TECHNICAL DATA SHEET FOR MORE INFORMATION GO TO www loctite com ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLER WATERWAY FAILURE TO DO SO MAY RESULT IN EQUIPMENT FAILURE INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT 6 7 5 4...

Страница 8: ...STALLATION TOOL 36 0 9 m BEAM ACCOMMODATES VARIETY OF FRAMING SPACINGS FACE OF WALL OR CEILING FRAMING MEMBER WIDE BASE OF BEAM FLUSH AGAINST FACE OF FRAMING MEMBERS ADJUST TO SUIT FRAMING SPACING AND FITTING LOCATION LOCK UNLOCK GAUGE CARRIAGE IMPERIAL SCALE 0 to 1 1 2 METRIC SCALE 0 to 40 mm GAUGE LOCK HANDLE LIP OF SPRINKLER BODY NOT BRASS SHOULDER FLUSH AGAINST SPRINKLER BODY STOP SURFACE ADJU...

Страница 9: ...CE OF FINISHED CEILING RAVEN STUDIO HORIZONTAL SIDEWALL SPRINKLER SPRINKLER FITTING THREAD ADAPTER ESCUTCHEON MOUNTING SURFACE SPRINKLER FITTING AND WATERWAY CENTERLINE 12 7 16 316 mm 4 7 16 133 mm REFERENCE DIMENSION D TOTAL CEILING OR WALL COVERING MATERIAL THICKNESS DRYWALL PLYWOOD ETC PLUS TAPE PLASTER ETC 1 NOTES CLEARANCE HOLE D REF PLASTER TAPE ETC CEILING OR WALL COVERING MATERIAL CEILING ...

Страница 10: ...he mount ing surface Damaged or altered sprin klers are to be replaced immediately to avoid personal injury and to prevent use for causing personal injury as well as to maintain the sprinkler system in an operative condition Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise alter...

Страница 11: ...ECTOR SPRINKLER DEFLECTOR ASSEMBLY IN OPERATED POSITION SPRINKLER DEFLECTOR ASSEMBLY IN OPERATED POSITION ESCUTCHEON ESCUTCHEON ESCUTCHEON MOUNTING SURFACE ESCUTCHEON MOUNTING SURFACE RAVEN STUDIO SPRINKLER RAVEN STUDIO SPRINKLER 4 102 mm TO 12 305 mm FACE OF FINISHED CEILING FIGURE 15 RAVEN STUDIO SPRINKLERS OPERATED CONDITION ...

Страница 12: ...nkler with shipping cap attached to remain in original packaging until ready for installation To avoid damage to link assembly do not pull cap away from sprinkler at an angle Step 3 Apply TEFLON tape sealant to external threads of thread adapter and install into sprinkler fitting A leak tight 1 2 in NPT thread adapter joint should be obtained by applying a minimum to maximum torque of 7 to 14 lb f...

Страница 13: ... Paint ceiling or wall to suit Note Paint cap to remain attached while painting ceiling or wall Note Install primed escutcheon for best painting results refer to Ordering Procedure Step 10 Orient escutcheon base flange toward mounting surface align ing escutcheon centerline with sprin kler centerline Push escutcheon onto sprinkler engaging body by prongs until flange is flush against mounting surf...

Страница 14: ...wrench prongs Ref Figures 1 7 and 8 Apply sealant to sprinkler inlet threads steel pipe system installations Ref Figure 9 CPVC pipe system installations Ref Figure 10 NOTICE Assure sealant avoids contact with internal waterway of sprinkler Failure to do so may result in equipment failure Step C Remove shipping cap from sprinkler by pulling away from body along sprinkler centerline NOTICE Sprinkler...

Страница 15: ...lant to set before proceeding to Step J 5 minutes for LOCTITE 243 30 minutes for PERM ABOND LH056 Step L Paint ceiling or wall to suit Note Paint cap to remain attached while painting ceiling or wall Note Install primed escutcheon for best painting results refer to Ordering Procedure Step K Orient escutcheon base flange toward mounting surface align ing escutcheon centerline with sprin kler center...

Страница 16: ...med White 56 306 0 004 Primed Grey 56 306 0 007 Custom Color 56 306 X 010 Stainless Steel White 56 307 4 010 Grey 56 307 7 010 Electropolish 56 307 9 010 Primed White 56 307 0 004 Primed Grey 56 307 0 007 Custom Color 56 307 X 010 Chrome coated appearance Style K Escutcheons 4 Inch Diameter Specify RAVEN Studio Sprinkler Escutcheon Style K 4 inch diameter specify material specify finish P N specif...