press ENTER).
Bcast
(List box:)
No: The value of the point will not be broadcast to be
used in logic on other controllers.
Send: The value of the point (whether it is ON or
OFF) will be available on the host network for use by
other controllers. Be sure that each sending Board-
Point combination is unique throughout the system. (If
the controller at address #01 is sending from its Bd-Pt
address 1-02, then no other controller can have an
output at its Bd-Pt address 1-02 sending.
Rec: The value of the point is being received from
another controller on the host network. You must enter,
in the Bd-Pt fields, the Bd-Pt address of the sending
point.
Bd-Pt
First enter the address of the RO board and point to
which the load is wired, or, in the case of a received
broadcast point, enter the board and point address of
the sending point.
On
(List box:)
Voltage: The point will be read as ON if it senses a
voltage. It will read OFF when it senses no voltage.
No Voltage: The point will be read as ON if it senses
no voltage. It will read OFF when it senses voltage.
Latching: The point will be read as ON when it first
senses a momentary voltage. It will continue to read on
when the voltage is no longer present. The point will
read OFF after voltage is applied again. This setting is
often used for push-button or other momentary-contact
sensing.
Closed: The input is on an AK2 I/O module, based on
a universal input. The input is on when continuity is
sensed at the universal input’s terminals. This is similar
to the reading of a closed dry contact input.
Open: The input is on an AK2 I/O module, based on a
universal input. The input is on when no continuity is
sensed at the universal input’s terminals. This is similar
to the reading of an open dry contact input.
SORT
At the bottom of the body of the screen (above the
icons, on the same line as “PG DN” for more is the
SORT field. By default, sort mode is on, and entries
will be sorted by Bd-Pt address; if sort mode is turned
off, points will be listed from then on in the order in
which they were created. The sorting occurs when you
press EXIT and will be apparent the next time you
enter the screen.
Содержание AK2-SC 255
Страница 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Страница 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Страница 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...
Страница 205: ...204 AK2 SC 255 Reference Manual RS 8D M1 22...