AK2-SC 255 Reference Manual
105
ClimaTECH
alarm configuration
ClimaTECH alarms are presented differently than most other alarms.
Alarm delay
(0 to 100) The number of minutes after an input
reaches trip level that an alarm will be generated. All
ClimaTECH alarms have a common alarm delay.
Each alarm has a setting (Normal, Critical, etc.) as explained in the Alarms appendix.
A trip level (a temperature, pressure, etc., or on-off state) can be set for each alarm.
ClimaTECH
schedule
configuration
Because the ClimaTECH can function as a stand-alone, it contains its own schedules.
They are set for each day and holiday in the same manner as lighting schedules.
Refer to the lighting schedule section for information on setting. If all schedules are
set to Relative, and the default zero settings are left for all schedules, then the
HVAC unit will operate based on the store open hours set in the Store Info screens.
ClimaTECH I/O
configuration
A ClimaTECH unit’s points must be allocated and assigned using the I/O points
screens.