AK2-SC 255 Reference Manual
RS.8D.M1.22
Notice the common alarm delay at the top of the screen. It can be set to any number
from 0 to 100. The units, minutes, can not be changed. The alarm types are:
High zone temp
Occurs when zone temperature is above a set temperature -999.9° to 999.9° for the
specified alarm delay.
Low zone temp
Occurs when zone temperature is below a set temperature -999.9° to 999.9° for the
specified alarm delay.
No Airflow
Occurs when zone humidity is above a set percentage (the field takes values from -
999.9 to 999.9) for a period of from 1 to 9999 seconds, minutes, or hours.
Phase Loss
The ClimaTECH controller has a digital input to sense signals from the HVAC
system’s phase loss detector. This alarm occurs when the phase loss input has sensed
a phase loss for the specified alarm delay. of from 0 to 100 minutes.
Inverter failure
The ClimaTECH controller has a digital input to detect failure of the HVAC system’s
inverter, if the system is a variable speed unit. This alarm occurs when the inverter
has been called for for the specified alarm delay of from 0 to 100 minutes, and proof
has not been sensed.
Fire
The ClimaTECH controller has a digital input to detect the HVAC system’s fire
alarm. This alarm occurs when the fire input has been ON for the specified alarm
delay. of from 0 to 100 minutes.
HVAC fire (if an HVAC fire stat is configured)
A digital alarm from the AKC 55 that can be enabled to occur when a fire stat
monitor reads on for a specified time period (0-9999 seconds, minutes, or hours). This
alarm is separate and distinct from the preceding one in that it does not originate from
the ClimaTECH controller. It is presented on this screen because it pertains to the
system whose alarms are being configured.
Configuring
Miscellaneous
alarms
Returning now to the main Alarm Configuration Menu, the next item after HVAC is
Miscellaneous. Using the the miscellaneous alarms screens, you can create custom
Содержание AK2-SC 255
Страница 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Страница 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Страница 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...
Страница 205: ...204 AK2 SC 255 Reference Manual RS 8D M1 22...