170
AK2-SC 255 Reference Manual
RS.8D.M1.22
progress.
For fixtures with AKV valves, the valve is closed
and the defrost control relay is ON. For fixtures with
KVQ valves, the valve is open or closed (according
to configuration by the user). Make sure that the
KVQ is configured to remain open during gas
defrost. The KVQ valve may not be used as a
suction stop.
Terminated defrost:
The Smart Case Controller has terminated defrost
and is waiting for other coordinated controllers (if
any) to terminate. The valve remains in the state it
was in during defrost. Refrigeration will not resume
until all coordinated defrosts have been terminated.
Start after defrost:
A transitional status following termination of defrost,
including drip down and fan delays.
After drip down, AKV valves begin to open at a
predetermined percentage for a maximum of two
minutes to establish minimum superheat. When fan
delay is finished and minimum superheat is reached,
status will change to Cut-in.
After drip down, KVQ valves operate normally until
the completion of fan delay, when status changes to
Normal Operation.
Valve in manual:
The valve has been set to a manual percentage by
override. Auto operation is suspended. When the
valve has been returned to Auto mode, the status will
change to Start-up for AKV valves, and to Normal
Operation for KVQ valves.
Box door shutdown:
Operation has been interrupted by opening of a box
door. When the door is closed, status will change to
Start-up.
External shutdown:
The fixture has been shut down using an external
switch attached to one of the Smart Case
Controller’s auxiliary on-off inputs. The input must
be configured using the AKC 16x Settings screen.
Sensor failure:
The Smart Case Controller has detected a failure of
one of the sensors configured for the fixture, either
Liquid In, Gas Out, Case/Box, or Defrost tempera-
Содержание AK2-SC 255
Страница 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Страница 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Страница 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...
Страница 205: ...204 AK2 SC 255 Reference Manual RS 8D M1 22...