RS.8D.M1.22
AK2-SC 255 Reference Manual
113
will be turned off.
Minimum ON time
(0 to 255) When lights are turned on, the number of
minutes that they must remain on before being turned
off.
Minimum OFF time
(0 to 255) When lights are turned off, the number of
minutes that they must remain off before being turned
on.
Enable dimmer output
(List box: Yes, No) Whether or not a dimmer variable
output will be controlled.
Target
(0 to 100) The photocell level that the controller will
seek to maintain by operation of the dimmer.
Minimum output
(0 to 100) The minimum dimmer level.
Reaction time
(List box: Slowest, Slow, Normal, Fast, Fastest) The
relative sensitivity of control to changes in photocell
level.
Override switch
(List box: Yes, No) Whether or not there is an override
switch assigned to the zone.
Override duration
(Time field: 00:00 to 23:59) The duration of an override
when the override switch is used.
Burglar override
(List box: Yes, No) When this zone’s lights are turned
off, whether they are to be turned on when a moni-
tored burglar alarm is sensed.
Pre delay
(0 to 600) When this zone’s lights are off and a burglar
override is called for, the number of minutes delay
before the zone is turned on.
Fire override
(List box: Yes, No) When this zone’s lights are turned
off, whether they are to be turned on when a moni-
tored fire alarm is sensed. There is no pre-delay for
fire alarms.
Lighting schedules are found on the next page(s).
Board & points
configuration
(lighting)
Board and points configuration must be completed for all types of points. Do this in
accordance with the appendix on board & point configuration.
Powerlink
configuration
Configuration of Powerlink lighting zones configuration is the same as for the SC 255
zones just discussed, except that the question Number of control relays is replaced
with Number of control points. These panels also require board and point setup and
initialization (see below).
Cutler-Hammer
configuration
Configuration of Powerlink lighting zones configuration is the same as for the SC 255
zones just discussed, except that the question Number of control relays is replaced
with Number of control points. These panels also require board and point setup and
initialization (see below).
Содержание AK2-SC 255
Страница 1: ...REFRIGERATION AND AIR CONDITIONING AK2 SC 255 Reference Manual Users Manual...
Страница 2: ...RS 8D M1 22 AK2 SC 255 Reference Manual 1 AK2 SC 255 Rack Controller System Reference Manual...
Страница 3: ...2 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 11: ...10 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 157: ...156 AK2 SC 255 Reference Manual RS 8D M1 22...
Страница 204: ...RS 8D M1 22 AK2 SC 255 Reference Manual 203...
Страница 205: ...204 AK2 SC 255 Reference Manual RS 8D M1 22...