Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
180
79
Heat pump
lockout release
differential
Heat pump would be resumed
when the outdoor air temperature
is recovered by differential above
the heat pump lockout
temperature.
2.
7
9
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
0
1
2
81
Cooling comfort
setting
Cooling comfort setting for VRT
control
2.
8
1
Eco
Mild
Quick
Powerful
0
1
2
3
82
Heating comfort
setting
Heating comfort setting for VRT
control
2.
8
2
Eco
Mild
Quick
Powerful
0
1
2
3
86
Optional setting
to prioritize VRT
control
Optional setting for VRT control to
save energy
2.
8
6
Prioritize largest demand
Prioritize smallest demand
0
2
89
Intermittent fan
operation
Used for intermittent fan operation
setting
2.
8
9
OFF
0
30 minutes OFF, 1 minute ON
with medium fan speed
1
30 minutes OFF, 1 minute ON
with high fan speed
2
90 Indoor unit
without power
Multi-tenant function setting
2.
9
0
Invalid
Valid
0
1
92
Te target
temperature
upper limit
Used to make setting of targeted
evaporating temperature upper
limit for cooling and heat recovery
operation.
2.
9
2
L
M
H
0
1
2
97
Auxiliary heater
maximum
allowable
temperature
Auxiliary heater is allowed to
energize when the ambient
temperature is smaller than the
auxiliary heater maximum
allowable temperature.
2.
9
7
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
12.7°C (55°F)
15.5°C (60°F)
18.3°C (65°F)
Auxiliary heater always not
allowed
Auxiliary heater always
allowed
1
1
1
1
1
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
98
Auxiliary heater
maximum
allowable
temperature
release
differential
Auxiliary heater is not allowed to
energize when the outdoor air
temperature is recovered by
differential above the auxiliary
heater maximum allowable
temperature.
2.
9
8
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
0
1
2
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
1: Numbers in the
No.
column represent the number of times to press the BS button.
: Setting does not return to factory setting when exit mode 2. To cancel the function, change
setting manually to factory setting.
: Once function is activated
t01
appears. To stop current function, press once the
RETURN
(BS3)
button. For detailed description about each setting, refer to
Details of Setting Mode 2
Indication
bold
means factory setting.
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...