Field Settings for Indoor Unit
SiUS342004EB
155
Part 5 Field Settings and Test Operation
1.3.18 Airflow Setting when Heating Thermostat is OFF
This setting is used to set airflow when heating thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to
03
(only remote
controller thermistor).
When thermostat OFF airflow volume up mode is used, careful consideration is required before
deciding installation location.
: Factory setting
1.3.19 Automatic Mode Differential
This setting makes it possible to change differential values for mode selection while in automatic
operation mode, only when the wireless remote controller or any central remote controller is
connected.
: Factory setting
The automatic operation mode setting is made by the use of the operation mode selector button.
1.3.20 Auto Restart after Power Failure
: Factory setting
When the Auto Restart after Power Failure setting is turned OFF, all the units will remain OFF after
power failure, or after the main power supply is restored. When this setting is turned ON (factory
setting), the units that were operating before the power failure will automatically restart operation
after power failure, or after the main power supply is restored.
Due to the aforementioned, when the Auto Restart after Power Failure setting is ON, be careful for
the following situations that may occur.
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
3
01
LL tap
02
Set fan speed
03
OFF
Mode No.
First Code
No.
Second Code No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
(0°F)
1°C
(1.8°F)
2°C
(3.6°F)
3°C
(5.4°F)
4°C
(7.2°F)
5°C
(9.0°F)
6°C
(10.8°F)
7°C
(12.6°F)
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
5
01
OFF
02
ON
1. The air conditioner will start operation suddenly after power failure,
or when the main power supply is restored. The user might be surprised
and wonder why the air conditioner turned ON suddenly.
2. During maintenance, if the main power supply is turned OFF while the
units are in operation, the units will automatically start operation
(the fan will rotate) after the power supply is restored due to completion
of the maintenance work.
Caution
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...