Outline of Control (Indoor Unit)
Part 4 Functions and Control
112
Assuming suction temperature has changed from 30°C (86°F) to 18°C (64°F) (F
A):
Suction air thermistor is used for temperatures from 30
C (86
F) to 25
C (77
F) (F
D).
Remote controller thermistor is used for temperatures from 25
C (77
F) to 21
C (70
F) (D
B).
Suction air thermistor is used for temperatures from 21
C (70
F) to 18
C (64
F) (B
A).
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near
the floor where the occupants are. When controlling by suction air thermistor only, the indoor unit
may therefore be turned off by the thermostat before the lower part of the room reaches the set
temperature. The temperature can be controlled so the lower part of the room where the occupants
are does not become cold by widening the range in which remote controller thermistor can be used
so that suction temperature is higher than the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 28°C (82°F) (A
D):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat sensor is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 25°C (77°F) (A
C).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 28°C (82°F) (C
D).
Assuming suction temperature has changed from 28°C (82°F) to 18°C (64°F) (D
A):
Remote controller thermistor is used for temperatures from 28°C (82°F) to 23°C (73°F) (D
B).
Suction air thermistor is used for temperatures from 23°C (73°F) to 18°C (64°F) (B
A).
Range in
w
hich remote controller
thermistor can be used
Range in
w
hich
suction air thermistor
can be used
Differential
Suction air temperature (TH1)
Set temperature (Ts)
12
14
16
1
8
20
22
24
26
2
8
30
32
34
53.6
57.2
60.
8
64.4
6
8
.0
71.6
75.2
7
8
.
8
8
2.4
8
6.0
8
9.6
93.2
°
C
°
F
°
C
32
30
2
8
26
24
22
20
1
8
16
°
F
8
9.6
8
6.0
8
2.4
7
8
.
8
75.2
71.6
6
8
.0
64.4
60.
8
TH1 = Ts + 12
≤
33
°
C
TH1 = Ts + 21.6
≤
91.4
°
F
TH1 = Ts + 10
≤
31
°
C
TH1 = Ts + 1
8
≤
8
7.
8
°
F
TH1 = Ts + 1
≤
31
°
C
TH1 = Ts + 1.
8
≤
8
7.
8
°
F
TH1 = Ts – 1
°
C
TH1 = Ts – 1.
8
°
F
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...