Field Settings for Outdoor Unit
SiUS342004EB
185
Part 5 Field Settings and Test Operation
[2-28]:
Power transistor check mode
To evaluate the output of the power transistors. Use this function in case error code
is displayed related to defective inverter PCB or compressor is locked.
Default value: 0. Power transistor check mode is not active.
Field setting 1: Power transistor check mode is active.
Function:
Inverter PCB gives output of 10 Hz in sequence by all 6 transistors. Remove the
U/V/W terminals of the compressor, and connect to the inverter checker module. If
all 6 LEDs blink, the transistors switch correctly.
When the power transistor check mode is interrupted, after internal power circuit
is disconnected on the inverter PCB, 2 LEDs will light up to indicate discharge of the
DC voltage. Wait till the LEDs are OFF before returning fasten terminals back to the
compressor terminals.
Minimum requirements to refer to the result on the inverter checker module:
All 3 phases and neutral are available, and
Inverter PCB control is active. Check if the green LED “HAP” on the inverter PCBs
are blinking normal (approx. 1/second). If LEDs are OFF, need to exit the “standby
mode” of the inverter:
Disconnect and reconnect power supply control PCB, or
Forced thermostat ON condition, or
Make shortly set 2-6-1 (forced thermostat ON indoor), or 2-20-1
(manual refrigerant charge).
Once the LED is blinking on the inverter PCB, change related setting
immediately back to set 0 to deactivate related function.
Diode module generates the required 750 VDC.
Cautions:
In case there is more than 1 compressor in a system (outdoor is multi outdoor
configuration) all compressor inverter PCBs will perform the power transistor check.
In such case, disconnect U/V/W fasten terminals on all compressors. Avoid
accidental touch of fasten terminals to short circuit or ground leak to casing.
To stop the power transistor check mode, change setting to default 2-28-0.
Output to U/V/W will also stop when outdoor unit main PCB decides standby
mode of inverter circuit.
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...