SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
156
Note(s)
Note(s)
1.3.21 Airflow Setting when Cooling Thermostat is OFF
This is used to set airflow to LL airflow when cooling thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to
03
(only remote
controller thermistor).
: Factory setting
1.3.22 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to
01
at the
factory.
1. The Second Code No. is factory set to Standard/All round outlet. For High ceiling (1) or (2),
initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
1. The Second Code No. is factory set to Standard/All round outlet. For High ceiling (1) or (2),
initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22)
6
01
LL tap
02
Set fan speed
03
OFF
FXFQ07-24AA, FXFQ07-24T
: Factory setting
Mode
No.
First
Code
No.
Second
Code No.
Setting
Ceiling Height
All round outlet
4-way outlets
3-way outlets
2-way outlets
13
(23)
0
01
Standard
Lower than
2.7 m
(8-3/4 ft)
Lower than
3.1 m
(10-1/8 ft)
Lower than
3.0 m
(10 ft)
Lower than
3.5 m
(11-1/2 ft)
02
High
Ceiling (1)
Lower than
3.0 m
(10 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.3 m
(10-3/4 ft)
Lower than
3.8 m
(12-1/2 ft)
03
High
Ceiling (2)
Lower than
3.5 m
(11-1/2 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
3.5 m
(11-1/2 ft)
—
FXFQ30-54AA, FXFQ30-48T
: Factory setting
Mode
No.
First
Code
No.
Second
Code No.
Setting
Ceiling Height
All round outlet
4-way outlets
3-way outlets
2-way outlets
13
(23)
0
01
Standard
Lower than
3.2 m
(10-1/2 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.6 m
(12 ft)
Lower than
4.2 m
(13-3/4 ft)
02
High
Ceiling (1)
Lower than
3.6 m
(12 ft)
Lower than
3.9 m
(12-3/4 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
4.2 m
(13-3/4 ft)
03
High
Ceiling (2)
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.5 m
(14-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
—
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...