SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
154
1.3.15 Optional Accessories Output Selection
Using this setting,
operation output signal
and
abnormal output signal
can be provided. Output
signal is output between terminals X1 and X2 of adaptor for wiring, an optional accessory.
: Factory setting
1.3.16 External ON/OFF Input
This input is used for ON/OFF operation and protection device input from the outside. The input is
performed from the T1-T2 terminal of the operation terminal block in the electrical component box.
: Factory setting
1.3.17 Thermostat Differential Changeover
Differential value during thermostat ON/OFF control can be changed.
Factory Setting
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided.
02
—
03
Output linked with ON/OFF of remote controller is provided.
04
In case of Error Display appears on the remote controller, output is
provided.
05
—
06
—
07
Only for FXSQ-TA, FXSQ-TB, FXMQ-PB, FXMQ-TB
Economizer (field supply) ON/OFF signal is provided.
Mode
No.
First Code
No.
Second
Code No.
Contents
12 (22)
1
01
ON: Forced stop (prohibition of using the remote controller)
OFF: Permission of using the remote controller
02
OFF
ON: Permission of operation
ON
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit indicates
A0
. The other
indoor units indicate
U9
.
04
—
05
Only for FXSQ-TA, FXMQ-PB
ON: Economizer (field supply) is connected.
OFF: Not connected
06
—
07
Only for FXSQ-TB, FXMQ-TB
ON: Economizer (field supply) is connected.
OFF: Not connected
F2 T1 T2
Forced stop
Input A
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
2
01
1°C (1.8°F)
02
0.5°C (0.9°F)
Model
Second Code No.
Contents
FXFQ-T, FXZQ-TA, FXUQ-P, FXEQ-P, FXSQ-TA, FXHQ-M,
FXTQ-TA, FXTQ-TB
01
1°C (1.8°F)
FXFQ-AA, FXZQ-TB, FXUQ-PA, FXDQ-M, FXSQ-TB,
FXMQ-PB, FXMQ-TB, FXMQ-TA, FXMQ-M, FXAQ-P,
FXLQ-M, FXNQ-M, FXMQ-MF, CXTQ-TA
02
0.5°C (0.9°F)
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...