Field Settings for Outdoor Unit
SiUS342004EB
199
Part 5 Field Settings and Test Operation
2.6.2 Demand Operation
By connecting the external contact input to the demand input of the outdoor unit external control
adaptor for outdoor unit (optional), the power consumption of unit operation can be saved
suppressing the compressor operating condition.
However, the demand operation does not occur in the following operation modes.
1. Startup control
2. Oil return operation
3. Defrost operation
4. Pump down residual operation
If carrying out demand or low noise input, connect the adaptor’s terminals as shown below.
A. When the demand operation is carried out by external contact (with the use of the
external control adaptor for outdoor unit).
1. Connect external control adaptor for outdoor unit and short circuit terminals as required (Refer
to the figure above).
2. While in setting mode 2, set the item 2-12 (External low noise or demand setting) to ON.
3. If necessary, while in setting mode 2, select a demand 1 level for the item 2-30.
B. When the Normal demand operation is carried out. (Use of the external control adaptor
for outdoor unit is not required.)
1. While in setting mode 2, set the item 2-32 (Setting of alternate demand) to ON.
2. While in setting mode 2, select a demand 1 level for the item 2-30.
Description of setting
Setting procedure
Setting item
Description
External control adaptor for
outdoor unit
Outdoor unit PCB
Demand 1 Operate with power of
70% or less of the rating.
Short circuit between 1 and C of
the terminal block (TeS1).
Set the item 2-32 to Demand 1.
Demand 2 Operate with power of
40% or less of the rating.
Short circuit between 2 and C.
Set the item 2-32 to Demand 2.
Demand 3 Operate with forced
thermostat OFF.
Short circuit between 3 and C.
—
Outdoor wiring indicated
by dotted line
External control
adaptor for outdoor unit
Host computer monitor
panel or demand controller
X
X
X
X
X
X
X
X
1
2
3
C
Demand
Low
noise
F1
F2
Host computer monitor panel or demand controller
If carrying out demand or low-noise input, connect the terminals
of the external control adaptor for outdoor unit as shown below.
To other external control adaptor
for outdoor unit
Outdoor
wiring
indicated by
dotted line.
X
X
X
X
X
X
X
X
1
2
3
C
Demand
Low
noise
F1
F2
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...