Field Settings for Outdoor Unit
SiUS342004EB
193
Part 5 Field Settings and Test Operation
2.5.4 Auxiliary Heat Control
To improve efficiency the auxiliary heat can be lockout based on outdoor temperature.
Item
Description
Min
Max
Increments
Auxiliary heater
allowable
temperature
Below this temperature, auxiliary
heater can be energized based on
the indoor temperature condition.
0°F
(−17.7°C)
65°F (18.3°C)
(Default
35°F (1.6°C))
5°F
(2.8°C)
Auxiliary heater
allowable
temperature
release differential
When the outdoor temperature
recovered by this temperature,
auxiliary heater cannot be allowed.
5°F, 10°F (default), 15°F
(2.8°C, 5.6°C (default), 8.3°C)
[2-97]:
Auxiliary heater maximum allowable temperature
Auxiliary heater is allowed to energize when the ambient temperature is smaller
than the auxiliary heater maximum allowable temperature.
Auxiliary heater
maximum allowable
temperature
Fahrenheit (°F)
Celsius (°C)
0
0
−17.7
1
5
−15
2
10
−12.2
3
15
−9.4
4
20
−6.6
5
25
−3.8
6
30
−1.1
7 (default)
35
1.6
8
40
4.4
9
45
7.2
10
50
10
11
55
12.7
12
60
15.5
13
65
18.3
14
Auxiliary heater always NOT allowed
15
Auxiliary heater always allowed
[2-98]:
Auxiliary heater maximum allowable temperature release differential
Auxiliary heater is not allowed to energize when the outdoor air temperature is
recovered by differential (below) above the auxiliary heater maximum allowable
temperature.
Auxiliary heater max allowable
temperature release differential
Fahrenheit (°F)
Celsius (°C)
0
5
2.8
1 (default)
10
5.6
2
15
8.3
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...