SiUS342004EB
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
186
Note(s)
Actual voltage value depends on multimeter characteristics (±143 VAC).
When operation parameters return to normal range, the capacity priority is switched OFF, enable to
reduce airflow rate depending on night-time low noise operation is still required (end time for
night-time low noise operation is not reached or external input night-time low noise operation is still
closed).
Next time graph shows the different steps during the power transistor check mode.
Switching sequence during power transistor check mode:
Power transistor check mode
disconnect fastened U/V/W from compressor!
Step 1:
Set 2-28
0 1
Press RETURN
twice
Step 2:
Set 2-28
1 0
Press RETURN
twice
Check
1
Check
2
Check
3
Magnet
switch
K1M
ON
Magnet
switch
K1M OFF
Voltage
output
U/V/W
Voltage
output
U/V/W
Frequency: 10 Hz
6 sec
3 sec
3 sec
30 sec
Check 4
Check
5
Check 1
: AC power input at terminals L1B, L2B, L3B (575 V unbalance maximum 2%).
Check 2
: DC voltage at connector X5A increases to ±750 VDC.
Check 3
: DC = 1.42 x VAC power supply at connector X5A
Check 4
: AC U/V/W 10 Hz intermediate
Check if difference is within 10 V (at fastened U/V/W).
Check 5
: Voltage drop (discharge capacitors DC)
Check if DC voltage at connector X5A increases to ±750 VDC.
note
[2-29]:
Capacity priority
When the night-time low noise operation is in use, performance of system might
drop because airflow rate of outdoor unit is reduced.
Default value: 0. Capacity priority cannot be used.
Field setting 1: Capacity priority can temporary cancel the night-time low noise
operation. Capacity priority can be initiated when certain operation parameters
approach the safety setting:
Raise in high pressure during cooling.
Drop in low pressure during heating.
Raise of discharge pipe temperature.
Raise of inverter current.
Raise of fin temperature inverter PCB.
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...