Field Settings for Outdoor Unit
SiUS342004EB
191
Part 5 Field Settings and Test Operation
Note(s)
The setting of [2-86] = 2 saves energy but may increase the time required to reach set point.
[2-82]:
Heating comfort setting for VRT control
Default value: 1.
Value
[2-82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
Change [2-82] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
When [2-82] is set to 0, the original refrigerant temperature target based on [2-9] is kept without
any correction, unless for protection control.
For more information and advice about the effect of these settings, refer to
Energy Saving and
Optimum Operation
[2-86]:
Optional setting to prioritize VRT control
Default value: 0.
Value
[2-86]
Level
0 (default)
Prioritize largest demand
2
Prioritize smallest demand
[2-89]:
Intermittent fan operation
Default value: 0.
Used for intermittent fan operation to assist snow discharge on outdoor fan.
Value
[2-89]
Intermittent fan operation
0 (default)
OFF
1
30 minutes OFF, 1 minute ON with medium fan speed
2
30 minutes OFF, 1 minute ON with high fan speed
[2-90]:
Indoor unit without power
U4
error generation.
In case an indoor unit needs maintenance or repair on the electric side, it is possible
to keep the rest of the
VRV
DX indoor units operating without power supply to some
indoor unit(s).
Default value: 0 (not active)
Field setting 1: It is possible to operate system without
U4
error when some indoor
units are temporarily without power supply.
Field setting 2: It is possible to operate system with
U4
warning when some indoor
units are temporarily without power supply.
Following conditions need to fulfil:
Maximum equivalent piping length of the farthest indoor less than 120 m (394 ft).
Index indoor units power simultaneously less than 30% of the nominal outdoor.
Total capacity is less than 30% of the nominal one of the outdoor unit.
Operation time is limited to 24 hours period.
It is recommended to shut down connected indoor units at the same floor.
Not possible to use service mode operation (e.g. recovery mode).
Backup operation has priority over this special feature.
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...