Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
198
Image of operation in the case of A
Image of operation in the case of B
Image of operation in the case of A and B
Operation
sound
Rated
Level 1
Level 2
Level 3
Approx. 55 dB (target)
Approx. 50 dB (target)
Approx. 45 dB (target)
Note 1: Above values are for reference only (measured in silent room)
Note 2: Above values are for 1 module only.
Operation sound level set with External low noise setting
If capacity priority is set in
Capacity priority setting, the fan
speed will be increased according
to the load of air conditioning
when load is heavier.
Operation sound
during low noise
mode can be set with
External low noise
level setting (Factory
setting is level 2.)
Low noise mode instructing
Operation
so
u
nd
Rated
Le
v
el 1
Le
v
el 2
Le
v
el 3
Time set with night-time low noise
operation start setting
If capacity priority is set in
Capacity priority setting, the fan
speed will
b
e increased
according to the load of air
conditioning when load is hea
v
ier.
Time set with night-time low
noise operation end setting
Operation so
u
nd d
u
ring
night-time low noise
operation mode can
b
e set
with night-time low noise
operation le
v
el setting.
(Factory setting is OFF.)
Night-time
Operation so
u
nd le
v
el set with
night-time low noise operation
setting
6:00 AM
8:00 PM 10:00 PM 12:00 AM
7:00 AM 8:00 AM
Set with night-time low noise operation end setting.
(Factory setting is 8:00 AM.)
Set with night-time low noise operation start setting.
(Factory setting is 10:00 PM.)
Operation
so
u
nd
Rated
Le
v
el 1
Le
v
el 2
Le
v
el 3
Time set with night-time low noise
operation start setting
Low noise mode
instr
u
cting
Operation so
u
nd set with
External low noise setting
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with night-time low noise operation start setting.
(Factory setting is 10:00 PM.)
Set with night-time low noise operation end setting.
(Factory setting is 8:00 AM.)
∗
Low noise
mode instr
u
cting
∗
Operation so
u
nd set with
External low noise setting
∗
Night-time
If capacity priority is set in
Capacity priority setting, the fan
speed will
b
e increased
according to the load of air
conditioning when load is hea
v
ier.
Time set with night-time low noise
operation end setting
Operation so
u
nd d
u
ring
low noise mode can
b
e
set with External
qu
iet
operation le
v
el setting. (Factory
setting is le
v
el 2.)
Operation so
u
nd d
u
ring
night-time low noise operation
mode can
b
e set with night-time
low noise operation le
v
el
setting. (Factory setting is OFF.)
When external low noise
instr
u
ction is recei
v
ed d
u
ring
the operation with night-time
low noise operation mode.
Le
v
el 2 precedes le
v
el 1 and
le
v
el 3 precedes le
v
el 2.
∗
Operation so
u
nd le
v
el set
with night-time low noise
operation setting
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...