Field Settings for Outdoor Unit
SiUS342004EB
173
Part 5 Field Settings and Test Operation
Mode 2
Mode 2 is used to set field settings of the outdoor unit and system.
Changing and access the setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds), you can select
the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
To quit and return to the initial status, press the
MODE (BS1)
button.
Changing the value of the selected setting in mode 2:
Once mode 2 is selected (press the
MODE (BS1)
button for more than 5 seconds) you can
select the wanted setting. It is done by pressing the
SET (BS2)
button.
Accessing the selected setting's value is done by pressing the
RETURN (BS3)
button once.
Now the
SET (BS2)
button is used to select the required value of the selected setting.
When the required value is selected, you can define the change of value by pressing the
RETURN (BS3)
button once.
Press the
RETURN (BS3)
button again to start operation according to the chosen value.
Example:
Checking the content of parameter [2-18] (to define the high static pressure setting of the outdoor
unit’s fan).
Mode: 2
Setting: 18
Make sure the segment indication is as during normal operation (default situation when shipped
from factory).
Press the
MODE (BS1)
button for over 5 seconds; result segment display:
Press the
SET (BS2)
button 18 times; result segment display:
Press the
RETURN (BS3)
button once; the value which is returned (depending on the actual
field situation), is the status of the setting. In the case of [2-18], default value is "0", which
means the function is not active.
Result: mode 2 setting 18 is addressed and selected, return value is the current setting situation.
To change the value of the setting, press the
SET (BS2)
button until the required value appears
on the segment indication. When achieved, define the setting value by pressing the
RETURN
(BS3)
button once. To start operation according to the chosen setting, confirm again by
pressing the
RETURN (BS3)
button.
To leave the field setting, press the
MODE (BS1)
button once, you will return to the default
situation when shipped from factory.
Operating the DIP
switches
For factory mounted board only use DIP switch DS1-1 if required.
Result: mode 2 accessed.
Result: mode 2 setting 18 is addressed.
DIP switch
Setting item
Description
No.
Setting
DS1-1
ON
COOL/HEAT
select
Used to choose source to select
Cooling/Heating/fan only. Source can be or indoor
remote controller, or optional cool/heat switch
wired to option BRP2A81.
OFF (Factory setting)
DS1-2
~DS1-4
ON
not used
Do not change the factory settings.
OFF (Factory setting)
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...