Field Settings for Outdoor Unit
SiUS342004EB
181
Part 5 Field Settings and Test Operation
2.5.3 Details of Setting Mode 2
Mode 2 is used to change the field settings of the system. Consulting the current field setting value
and changing the current field setting value is possible.
In general, normal operation can be resumed without special intervention after changing field
settings.
Some field settings are used for special operation (e.g. 1 time operation, recovery/vacuuming
setting, adding refrigerant setting, etc.). In such a case, it is required to abort the special operation
before normal operation can restart. It will be indicated in below explanations.
[2-0]:
Cool/Heat selection setting
Cool/Heat selection setting is used in case the optional Cool/Heat selector
(KRC19-26A) is used. Depending on the outdoor unit setup (single outdoor unit setup or
multi outdoor unit setup), the correct setting should be chosen. More details on how to
use the Cool/Heat selector option can be found in the manual of the Cool/Heat selector.
Default value: 0.
0: Each individual outdoor unit can select Cool/Heat operation (by Cool/Heat selector
if installed).
1: Master unit decides Cool/Heat operation when outdoor units are connected in
multiple system combination
2: Slave unit for Cool/Heat operation when outdoor units are connected in multiple
system combination
Change [2-0] to 0, 1 or 2 in function of required functionality.
[2-1]:
Cool/Heat unified address
Address for cool/heat unified operation.
When multiple heat pump systems need to change over together between cooling
and heating (example multiple systems serve indoor units in landscape area). Per zone
the optional PCB DTA104A61/62 needs to be installed. Recommended location is in
one of the
VRV
indoor units belonging to the system that will be set as “Master cool/heat
unit” (field setting 2-0-1).
The address set to the multiple systems need to operate as a zone, should be same
as the address set by the DIP switches on the related optional PCB DTA104A61/62.
External
control adaptor
for outdoor unit
No.0
Outdoor
unit group
master No.0
Outdoor
unit group
slave No.0
Outdoor
unit group
slave No.0
Outdoor
unit group
master No.2
Outdoor
unit group
slave No.2
Outdoor
unit group
slave No.2
Outdoor
unit group
master No.1
Outdoor
unit group
slave No.1
Outdoor
unit group
master No.3
Outdoor
unit group
slave No.3
External
control adaptor
for outdoor unit
No.1
External
control adaptor
for outdoor unit
No.2
External
control adaptor
for outdoor unit
No.3
DS2, DS1
DS2, DS1
DS2, DS1
DS2, DS1
C/H group address
C/H group address
C/H group address
C/H group address
Содержание VRV RXYQ72-384XAYCA
Страница 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Страница 366: ...Check SiUS342004EB 359 Part 6 Service Diagnosis Reference Reference CHECK 7 Refer to page 364 CHECK 8 Refer to page 365...
Страница 391: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 384 1 Wiring Diagrams 1 1 Outdoor Unit RXYQ72 96 120 144 168XAYCA 2D119209B...
Страница 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Страница 396: ...Wiring Diagrams SiUS342004EB 389 Part 7 Appendix BYCQ125BGW1 Self Cleaning Decoration Panel for FXFQ T 3D076375A...
Страница 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Страница 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Страница 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Страница 403: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 396 FXSQ05 07 09 12 15 18 24 30 36 48 54TAVJU C 3D110467C...
Страница 405: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 398 FXMQ07 09 12 15 18 24 30 36 48 54PBVJU 3D093209B...
Страница 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Страница 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Страница 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...