Troubleshooting by Error Code
SiME281906E
139
Part 6 Service Diagnosis
Note(s)
Reference
5.11 Thermistor Abnormality
Applicable
Models
All indoor unit models
Error Code
C4, C5, C9
Method of Error
Detection
The error is detected by temperature detected by thermistor.
Error Decision
Conditions
The thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defective connector connection
Defective thermistor
Defective indoor unit control PCB
Broken or disconnected wire
Troubleshooting
Error code and thermistor
CHECK 1
Refer to page 192.
Normal.
(Defective connector
connection)
Does it function normally?
Replace the indoor unit
control PCB (A1P).
(Defective PCB)
YES
Disconnect the thermistor on the PCB
and connect again.
Disconnect the thermistor on the PCB
and measure the resistance with a
multimeter.
NO
YES
Replace the thermistor.
(Defective thermistor)
Is it normal?
NO
CHECK 1
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error Code
Thermistor
Symbol
C4
Indoor heat exchanger liquid pipe thermistor
R2T
C5
Indoor heat exchanger middle thermistor
R3T
C9
Suction air thermistor
R1T
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...