Troubleshooting by Error Code
SiME281906E
129
Part 6 Service Diagnosis
5.3 Error of External Protection Device
Applicable
Models
All indoor unit models
Error Code
A0
Method of Error
Detection
Detect open or short circuit between external input terminals in indoor unit.
Error Decision
Conditions
An open circuit occurs between external input terminals with the remote controller set to
external ON/OFF terminal.
Supposed
Causes
Activation of external protection device
Improper field setting
Defective indoor unit PCB
Troubleshooting
Activation of external
protection device.
External
protection device is
connected to terminals T1 and
T2 of the indoor unit
terminal block.
Replace the indoor unit
control PCB (A1P).
YES
Change the second code
No. to
01
or
02
.
External
ON/OFF input (mode
No. 12, first code No. 1) has
been set to external protection
device input (second code
No. 03) by remote
controller.
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check the setting state of the
ON/OFF input from outside by remote
controller.
NO
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...