Troubleshooting by Error Code
SiME281906E
177
Part 6 Service Diagnosis
Reference
Reference
CHECK 4
Refer to page 196.
CHECK 7
Refer to page 198.
Replace the outdoor unit main PCB
(A1P).
NO
Monitor the voltage. (Instantaneous
voltage drop)
(Voltage fluctuation due to an in-house
generator)
YES
Is the
measured voltage 220
VDC or more?
While the compressor is running,
measure the voltage between C+ and
C– of power module.
Replace the outdoor unit main PCB
(A1P).
Connect the fan motor and
operate?
NO
YES
Connect the wires correctly.
Are the power
supply and compressor
connections correct? Is
there open
phase?
NO
YES
A
CHECK 4