Troubleshooting by Error Code
SiME281906E
183
Part 6 Service Diagnosis
Reference
CHECK 7
Refer to page 198.
Are the
resistance values between
pins balanced within
±20%?
NO
YES
NO
Replace the indoor unit PCB.
External factor (Noise, etc.)
External factor (Noise, etc.)
Is the error code
U4
displayed?
YES
Error is displayed again.
NO
YES
After turning OFF the power supply,
correctly insert the connector of the
fan motor and then restore the power.
Replace the outdoor unit main
PCB (A1P).
Check the resistance value of the
outdoor fan motor.
A
B
CHECK 7
Is HAP on the
outdoor unit main PCB
blinking?
Replace the outdoor fan
motor.
YES
NO
Turn OFF the power supply and
disconnect the connector of the
outdoor fan motor. Then power ON
again.
Replace the outdoor fan motor.