Troubleshooting by Error Code
SiME281906E
137
Part 6 Service Diagnosis
5.10 Transmission Error (between Indoor Unit PCB and Fan
PCB)
Applicable
Models
All indoor unit models
Error Code
C1-01
Method of Error
Detection
Check the condition of transmission between the indoor unit control PCB and the fan PCB using
microcomputer.
Error Decision
Conditions
Error is decided when transmission between the indoor unit control PCB and the fan PCB has
been lost for 15 seconds and the error code will be displayed on the remote controller 60
seconds later.
Supposed
Causes
Defective connection of the transmission connector between the indoor unit PCB and the fan
PCB
Defective indoor unit control PCB
Defective fan PCB
External factor such as noise