SiME281906E
Troubleshooting by Error Code
Part 6 Service Diagnosis
160
Reference
Troubleshooting
RZF30/36AVMK
CHECK 7
Refer to page 198.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Request an improvement to
make the power supply
voltage fall within the standard
range.
Is the power
supply voltage within the
standard range?
Are the
resistance values between
pins balanced within
±20%?
Does the fuse
F6U have continuity?
External factor (Noise, etc.)
NO
Connect the lead wire tightly
and correctly.
NO
NO
Replace the fuse.
Use only specified fuse.
NO
NO
Turn OFF the power supply.
Disconnect the fan motor connector
and restart operation.
Replace the outdoor unit main
PCB (A1P).
YES
YES
Power ON again.
Replace the fan motor.
YES
Replace the fan motor.
NO
YES
Check the resistance value for the fan
motor.
YES
Error is displayed again.
Error is displayed again.
YES
CHECK 7
Is the
compressor lead
wire securely connected to
the PCB and compressor?
Is there open
phase?
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...