Field Settings from Demand Adaptor (For 30/36 Class)
Part 5 Field Settings and Test Operation
80
2. Field Settings from Demand Adaptor (For 30/36
Class)
2.1 i-Demand Function
Purpose
Set a limitation towards the power consumption from the system. (e.g. budget control, limit
power consumption during peak moments,..)
Setting
1. Connect the power supply connector from X81A on the demand adaptor to X77A on the
outdoor unit PCB.
2. Connect the transmission connector from X80A on the demand adaptor to X6A on the
outdoor unit PCB.
3. Short-circuit the contacts on the terminal X801M according to the desired demand.
4. Set the dip switch DS1 if required.
Power supply connector
(on outdoor unit PCB X77A)
Transmission connector
(on outdoor unit PCB X6A)
Output on X801M: 12 VDC, 12 mA
Maximum wire length: 100 m
3
2
1 LNOP
COM
X801M
2
1 LNOP COM
X80A
X800M
X81A
DS1
ON
OFF
1 2 3 4
X801M
3
Demand
Maximum power
consumption
Terminal (X801M)
Dip switch (DS1)
1
2
3
4
Switch position
Demand 1
100%
Short-circuit the contacts
COM and 1.
ON
ON
OFF
OFF
80%
OFF
ON
OFF
OFF
70%
ON
OFF
OFF
OFF
60%
OFF
OFF
OFF
OFF
(factory setting)
Demand 2
40%
Short-circuit the contacts
COM and 2.
—
Demand 3
Forced
thermostat OFF
Short-circuit the contacts
COM and 3.
—
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...