Troubleshooting by Error Code
SiME281906E
127
Part 6 Service Diagnosis
Error code
Troubleshooting
Description of error
Diagnosis
LC - 01
Defective wiring
Defective transmission including that caused when the power
supply turns ON. This error is supposed to have resulted from
(1) defective wire connections around the PCB,
(2) defective outdoor unit main PCB, or (3) defective fan motor.
Check and probe the cause.
LC - 02
Defective transmission between compressor and
microcontroller
There is an error in transmission between the compressor and
the outdoor unit main PCB. If the wire connections of the
compressor are normal, check for the same of the outdoor unit
PCB.
LC - 03
Transmission error (main PCB)
Refer to the
LC
flowchart and check the wiring status at the
relevant location and the PCB.
LC - 04
Transmission error (main PCB)
LC - 05
Transmission error
P4 - 01
Power module thermistor malfunction (inverter)
(30/36 class only)
Check whether the power module thermistor X111A has come
loose.
PJ - 01
Capacity setting undefined
This is an outdoor unit main PCB for repair, but has no
capacity setting adaptor connected. Connect a correct capacity
setting adaptor to the PCB.
PJ - 04
Defective capacity setting
This error results from a mismatch of signals between the
controller in the PCB and the inverter. Check whether the type
of the PCB is correct and correct capacity setting adaptor is
connected.
U0 - 02
Refrigerant shortage - Outdoor unit (Factor 0)
This error results from a shortage of refrigerant. Refer to the
U0
flowchart and make a diagnosis, and then take
countermeasures.
U0 - 03
Refrigerant shortage - Outdoor unit (Gas leakage) This error results from a shortage of refrigerant cause by gas
leakage. Charge refrigerant up to the normal refrigerant
amount.
U0 - 04
Refrigerant shortage - Outdoor unit (Clogging)
This error results from clogging caused somewhere in the
refrigerant piping system. Check for a failure to open the stop
valve and clogging in the refrigerant system.
U0 - 12
Refrigerant cooling condensation error
Insufficient refrigerant may have caused the temperature of the
refrigerant cooling parts to drop, leading to condensation.
Refer to the
U0
flowchart to diagnose and handle this error.
U0 - 14
Refrigerant shortage - Outdoor unit (Cooling)
This error results from a shortage of refrigerant. Refer to the
U0
flowchart and make a diagnosis, and then take
countermeasures.
U1 - 01
Frequency judgment abnormality
Checks for power supply frequency abnormality. Check for
faulty power supply wiring.
U2 - 01
Power supply voltage error
This error is supposed to have resulted from undervoltage or
overvoltage of the power supply, or defective voltage sensor in
the PCB.
U2 - 02
Open phase of power supply
Check for any open phase of the power supply.
U2 - 03
Main circuit capacitor charge error
There is abnormal circuit current flowing in the PCB. If wire
connections related to the PCB are normal, replace the
outdoor unit main PCB.
U2 - 04
SP/MP - PAM overvoltage error
There is an overvoltage error (Single phase). If wire
connections related to the PCB are normal, replace the
outdoor unit main PCB.
U2 - 35
AC voltage sensor error
A voltage sensor failure within the PCB has been detected.
Refer to the
U2
flowchart and diagnose the appropriate PCB.
UA - 01
Incorrect number of indoor units connected
This error will be displayed if the locally-set number of indoor
units is different from the detected number of indoor unit.
UA - 02
Multiple master units detected
There are a number of indoor units with a remote controller
connected.
Connect the remote controller to only one indoor unit.
UA - 03
Excess indoor units connected
This error will be displayed if 5 or more indoor units are
connected.
UA - 05
Indoor-outdoor transmission error between slave 1
and outdoor unit
There is an error in transmission between the outdoor unit and
slave indoor unit 1. Check for the connection of the jumper
between the slave indoor unit (with no remote controller
connected) and the outdoor unit.
UA - 07
Indoor-outdoor transmission error between slave 2
and outdoor unit
There is an error in transmission between the outdoor unit and
slave indoor unit 2. Check for the connection of the jumper
between the slave indoor unit (with no remote controller
connected) and the outdoor unit.
UA - 09
Indoor-outdoor transmission error between slave 3
and outdoor unit
There is an error in transmission between the outdoor unit and
slave indoor unit 3. Check for the connection of the jumper
between the slave indoor unit (with no remote controller
connected) and the outdoor unit.
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...