Part 6 Service Diagnosis
168
5.29 Transmission Error between Microcomputers on
Outdoor Unit Main PCB
Applicable
Models
All outdoor unit models
Error code
LC
Method of Error
Detection
Check whether transmission between microcomputers on the outdoor unit main PCB is carried
out normally.
Error Decision
Conditions
The transmission is not carried out normally in a specified period of time.
Supposed
Causes
Defective outdoor unit main PCB
External factor (Noise, etc.)
Defective outdoor fan motor
Defective connection of fan motor connector
Troubleshooting
Connect the connector, and
turn ON again.
Is the fan motor
connector connected properly to
the outdoor unit main
PCB?
NO
YES
Replace the outdoor unit main
PCB (A1P).
Disconnect the fan motor connector,
and turn ON again.
NO
Replace the fan motor.
Inverter transmission
error due to the error of
fan motor.
Is the error
code
E7
displayed? (Is
LC
not displayed?)
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...