Field Settings from Outdoor Unit PCB (For 30/36 Class)
Part 5 Field Settings and Test Operation
84
3.3 Monitor Mode (Mode 1)
In the monitor mode, information can be retrieved about current operation status (normal, oil
return), outdoor unit class, errors/retries, and cause of stepping-down operation.
3.3.1 How to Retrieve Data
Selecting monitoring item
SEG1 SEG2 SEG3
Normal
Normal
: hold 5 seconds
: BLINKS
: ON
: OFF
Legend Segment
MODE
BS1
MODE
BS1
RETURN
BS3
RETURN
BS3
SET
BS2
Checking for description of data
Press the
SET (BS2)
button to set
the 7 segment display to any of the
monitoring items listed in the table below.
Press the
RETURN (BS3)
button.
Data on the monitoring item selected will
appear on the 7 segment display.
Press the
MODE (BS1)
button will return
the mode to normal mode.
Press the
RETURN (BS3)
button to
set monitor mode to the initial state.
∗
If you lose setting in progress,
press the
MODE (BS1)
button.
You should return to normal mode.
To enter monitor mode, press the
MODE (BS1)
button while in
normal mode.
Содержание SkyAir RZF-A Series
Страница 1: ...Service Manual RZF A Series Cooling Only 50 60 Hz SiME281906E ...
Страница 209: ...SiME281906E Part 7 Appendix 204 1 Wiring Diagrams 205 1 1 Indoor Unit 205 1 2 Outdoor Unit 206 Part 7 Appendix ...
Страница 210: ...Wiring Diagrams SiME281906E 205 Part 7 Appendix 1 Wiring Diagrams 1 1 Indoor Unit FDMF18 24 30 36AVMK 3D122556A ...
Страница 211: ...SiME281906E Wiring Diagrams Part 7 Appendix 206 1 2 Outdoor Unit RZF18 24AVMK 3D122453A ...
Страница 212: ...Wiring Diagrams SiME281906E 207 Part 7 Appendix RZF30 36AVMK 3D122423B ...